28

„

Read Alarm or Warning (ALM_RD)

The ALM_RD command is used to read the following information about the status of faults 
and alarms.

•  Present fault and alarm status list
•  Fault history (Alarms are not saved in the history.)
•  Details of faults

In the following case, a warning is generated and the command is ignored.

•  If ALM_RD_MOD is other than a set value: Data setting alarm (A.94)

The fault history is saved in EEPROM and is kept even when the control power is inter-
rupted.

The following table shows the specifications for ALM_RD_MOD and ALM_DATA.

If the fault history (ALM_RD_MOD = 1) is selected, the fault code (1 byte) is entered in 
order of detection from ALM_DATA byte 6, and byte 6 is refreshed with the most recent 
fault code.  If no fault occurred, 00H is displayed to indicate normal operations.

Byte

Command

Response

1

ALM_RD

ALM_RD

2

ALARM

3

STATUS

4

5

ALM_RD_MOD

ALM_RD_MOD

6

ALM_DATA

7

8

9

10

11

12

13

14

15

16

WDT

RWDT

ALM_RD_MOD

ALM_DATA

Max. 

Processing Time

Constant No.

0

Present fault (byte 6), past fault (byte 7)

0.1 s

n178 (Fault History)

1

Fault history (Alarms are not retained in the history.) 
2 max. (bytes 6 and 7)*

0.1 s

n178

Содержание VS mini V7

Страница 1: ...YASKAWA VS mini V7 OPTION UNIT MECHATROLINK COMMUNICATIONS INTERFACE UNIT USER S MANUAL YASKAWA MANUAL NO SIBP C730600 03A Model SI T V7...

Страница 2: ...liability is assumed with respect to the use of the information contained herein Moreover because Yaskawa is con stantly striving to improve its high quality products the information contained in this...

Страница 3: ...on General Precautions The diagrams in this manual may be indicated without covers or safety shields in order to show details Be sure to restore covers or shields before operating the Inverter and ope...

Страница 4: ...result in loss of life or seri ous injury Indicates precautions that if not heeded could result in relatively less serious or minor injury or damage to the equipment Failure to heed even a precaution...

Страница 5: ...icators have turned OFF The time is shown on the Inverter s front cover Failure to do so can result in electric shock Do not allow cables to be damaged subjected to stress placed under heavy objects o...

Страница 6: ...e However if the Yaskawa Authorized Service Center determines that the problem with a Yaskawa product is not due to defects in Yaskawa s workmanship or materials then the cus tomer will be responsible...

Страница 7: ...power or under water use must contact their Yaskawa representatives or the nearest Yaskawa sales office beforehand This product has been manufactured under strict quality control guidelines However i...

Страница 8: ...ling the SI T V7 Unit 15 4 2 MECHATROLINK Communications Cables 17 5 Transmission Interface 18 5 1 MECHATROLINK II Cyclic Transmissions 18 5 2 Basic Format of Data Transfer 19 5 3 Communications Phase...

Страница 9: ...cing of the settings for the Inverter constants from the host controller The SI T V7 Unit can be installed in the following Inverters VS 606V7 series Inverters software version No 565X VS 606V7 series...

Страница 10: ...hat was ordered Check the information printed on the Unit Refer to 2 1 Nameplate Has the product been damaged in any way Inspect the entire exterior of the Unit for any damage that may have occurred d...

Страница 11: ...MECHATROLINK II The following table shows the pin num bers and their functions 5 5 mm LED Communications connector CN2 Communications connector CN2 DIP switch Modular plug CN10 Rotary switch Optional...

Страница 12: ...tting error or Inverter model code error ERR Red Lit Watchdog timeout error communications error or resetting hard ware Red Blinking ROM check error once RAM check error twice DPRAM check error 3 time...

Страница 13: ...Label Status Function Factory Setting Baud rate S1 1 OFF 4 Mbps MECHATROLINK I 1 ON ON 10 Mbps MECHATROLINK II Data length S1 2 OFF 17 byte data transmission MECHATROLINK I MECHATROLINK II ON ON 32 by...

Страница 14: ...of the station number OFF 2 2X ON 3 3X S2 Set the 1 s digit of the station number 0 0 X0 1 1 X1 x x x x F F XF Switch Setting and Station Number SI 3 S2 Station Number S1 3 S2 Station Number OFF 0 Fa...

Страница 15: ...eces do fall in be sure to remove them 4 Align the mounting fixture with the C tab and use M3 8 SW screws to secure the fix ture B 5 Before installing the SI T V7 Unit on the Inverter connect the grou...

Страница 16: ...Inverter Fig 2 Front of the SI T V7 Unit 5 5 mm CN1 CN2 5 5 mm Mounting fixture Connector for SI T V7 Unit CN2 Modular plug CN1 Modular plug CN10 Grounding cable blue To Inverter ground terminals Gro...

Страница 17: ...trical and power lines Connect the terminator model No JEPMC W6022 on the end of the communication lines Maximum transmission distance is 50 m Minimum wiring distance between stations is 0 5 m Commun...

Страница 18: ...roller are executed by sending response data timed to the reception of command data for the local station address from the controller in each transmission cycle The formats for the command and respons...

Страница 19: ...ransfer 17 byte mode Basic format of data transfer 32 byte mode Command data Station address Control code Command code Data WDT Response data Header of data link layer Data link layer data and applica...

Страница 20: ...2 Asynchronous communications All SI T V7 commands can be used Phase 2 starts to count the watchdog timer in the com munications frame The phase moves to phase 3 when a SYNC_SET command is received a...

Страница 21: ...command or a sub command is already being processed the command being processed is given priority If an INV_CTL main com mand and an INV_I O sub command conflict the sub command overwrites the main co...

Страница 22: ...stant No Name Description Default n003 Operation Method Selec tion 0 Digital Operator 1 Control circuit terminal 2 MEMOBUS communications 3 Communications Card optional 0 n004 Frequency Reference Sele...

Страница 23: ...ands The format of the main commands are as follows No Operation NOP Only the ALARM and STATUS fields of the response data can be monitored This command can be used in all phases Byte Command Response...

Страница 24: ...n 32 byte mode Command alarm A 95 If a register number NO fault occurs User constant setting alarm A 94 If SIZE is an odd number or is not between 2 and 8 User constant setting alarm A 94 The register...

Страница 25: ...ceived as a main command in 32 byte mode Command alarm A 95 If a register number NO fault occurs User constant setting alarm A 94 If SIZE is an odd number or is not between 2 and 8 User constant setti...

Страница 26: ...as well as the portions show ing the structure are represented by spaces 2 Indicates the voltage class 2 200 VAC input 4 400 VAC input 3 Indicates the maximum applicable motor capacity For 0 1 kW 0P1...

Страница 27: ...d If not in phase 2 or 3 Command alarm A 95 If CONFIG_MOD is not a set value Data setting alarm A 94 The following values can be assigned to CONFIG_MOD Byte Command Response 1 CONFIG CONFIG 2 ALARM 3...

Страница 28: ...rupted The following table shows the specifications for ALM_RD_MOD and ALM_DATA If the fault history ALM_RD_MOD 1 is selected the fault code 1 byte is entered in order of detection from ALM_DATA byte...

Страница 29: ...to clear the status of the alarm or warning In the following cases a warning is generated and the command is ignored If not in phase 2 or 3 Command alarm A 95 If ALM_CLR_MOD is other than a set value...

Страница 30: ...ies the following formulas When the transmission cycle is equal to the communications time COM_TIM 1 32 byte data transmission 1 ms transmission cycle ms 8 ms If the transmission cycle is set to a fra...

Страница 31: ...t to 1 for Ver 1 0 VER 10H Data setting alarm A 94 If D6 D5 D4 D3 or D0 is set to 1 Data setting alarm A 94 For details on the transmission cycle communications time and communications phases refer to...

Страница 32: ...ission faults is executed This command can be used in phases 2 and 3 If this command is received while in phase 2 or 3 the data for the control command to the Inverter is cleared to 0 and a fault rese...

Страница 33: ...nals refer to the following table The speed reference unit can be selected with n035 The torque reference is used for both positive and negative values in units of 0 1 Byte Command Response 1 INV_CTL...

Страница 34: ...ration 2 INV multi function terminal input 3 Default External fault EF3 3 INV multi function terminal input 4 Default Fault reset 4 INV multi function terminal input 5 Default Multi step speed referen...

Страница 35: ...ding to n035 2 Torque reference U 08 0 1 Given only for vector control 3 Not used 4 Frequency reference U 01 According to n035 5 Pulse train reference RP 0 1 6 Main circuit current voltage 1 V 7 Inver...

Страница 36: ...are carried out If communica tions become asynchronous due to any fault such as a communications fault this command can be used to restore synchronous communications In the following case a warning is...

Страница 37: ...mmands are as follows Sub commands can be used only with MECHATROLINK II when the 32 byte mode has been selected by a switch No Operation NOP This is the format of No Operation sub command Byte Comman...

Страница 38: ...mmand is ignored If a warning is generated the values that were read are undefined While using the Digital Operator to change settings Command alarm A 95 If a register number NO fault occurs User cons...

Страница 39: ...are undefined While using the Digital Operator to change settings Command alarm A 95 If not in phase 2 or 3 Command fault A 95 During an undervoltage error Command alarm A 95 If a register number NO f...

Страница 40: ...not in phase 2 or 3 Command fault A 95 Read Alarm ALM_RD The ALM_RD sub command is used to read the fault and alarm status This sub command functions in the same way as the ALM_RD main command In the...

Страница 41: ...is the same as that for the SEL REF1 2 command in the INV_CTL main command The SEL MON3 4 sub command is used to select the contents of MON3 with bits 0 to 3 and select the contents of MON4 with bits...

Страница 42: ...Inverter or during baseblock 0 Baseblock ON 1 Baseblock OFF 4 PON Main power supply ON OFF during undervoltage 0 Main power supply OFF 1 Main power supply ON 5 RUNX Running 0 1 Running 6 0SP Zero spe...

Страница 43: ...lue of 0 is always returned D7 D6 D5 D4 D3 D2 D1 D0 SUBCMDRDY SBWARNG SBALM Bit Name Description Value Setting D0 SUBALM Sub command alarm 0 No alarm 1 Alarm D1 SUBWARNG Sub command warning 0 No warni...

Страница 44: ...otification pri ority is given to the warning with the lowest warning code If alarms and warnings are mixed together the SI T V7 gives notification priority to alarms The following table shows the res...

Страница 45: ...r warning code 1 0 Table 7 Reception Failures in Each Phase Communications Phase Reception Failure Transmission cycle First Second Consecutive Fault Phase 1 Phase 2 96 E6 E6 Phase 3 96 E6 E6 Table 8 A...

Страница 46: ...urs 94 Data setting warning Communications warning Received commands are ignored 95 Command warning Communications warning Received commands are ignored EC WDC fault with Inverter Communications alarm...

Страница 47: ...nverter overheat 0BH OL1 Motor overload 0CH OL2 Inverter overload 0DH OL3 Overtorque 1 10H RH Braking resistor overheat 5 5 7 5 kW only 11H EF3 External fault 3 12H EF4 External fault 4 13H EF5 Extern...

Страница 48: ...ional communi cations error Communications are not established with the host controller Check the LED indicators Check the communications cable wiring E5 SI T WDT error There is no continuity in the W...

Страница 49: ...communications cycle 21 stations max 21 slaves can be set but then the maximum num ber of connectable Inverters will be 16 For MECHATROLINK II 32 byte transmission 1 ms communications cycle 9 station...

Страница 50: ...f the revised manuals are given on the bottom of the back cover Date of Printing Rev No Section Revised Content January 2005 First edition MANUAL NO SIBP C730600 03A Printed in Japan January 2005 05 1...

Страница 51: ...Fax 86 21 5385 3299 YATEC ENGINEERING CORPORATION 4F No 49 Wu Kong 6 Rd Wu Ku Industrial Park Taipei Taiwan Phone 886 2 2298 3676 Fax 886 2 2298 3677 YASKAWA ELECTRIC HK COMPANY LIMITED Rm 2909 10 Ho...

Отзывы: