5 Transmission Interface
21
5.4
Application Layer Specifications
The data format for the application layer conforms to the MECHATROLINK-II link com-
mand specifications. The SI-T/V7 has the following main commands and sub-commands.
The main commands are used in both the 17-byte and 32-byte modes for
MECHATROLINK-II and with MECHATROLINK-I. The sub-commands can be used only
when the 32-byte mode has been selected by means of pin 2 on DIP switch S1. If a conflict
occurs between a request for a main command and a request for a sub-command, the request
for the main command is processed. If either a main command or a sub-command is already
being processed, the command being processed is given priority. If an INV_CTL main com-
mand and an INV_I/O sub-command conflict, the sub-command overwrites the main com-
mand.
For details on command formats, refer to
Chapter 7 MECHATROLINK-II Commands
.
Table 1 Main Commands
Name
Function
NOP
No Operation
PRM_RD
Reads Parameters.
PRM_WR
Writes Parameters.
ID_RD
Reads ID numbers.
CONFIG
RAM Write ENTER_CODE and EEPROM Write
ENTER_CODE
ALM_RD
Reads fault and alarm.
ALM_CLR
Clears fault and alarm.
CONNECT
Connect
DISCONNECT
Disconnect
INV_CTL
Controls Inverter Operation.
SYNC_SET
Starts Synchronous Communications.
Table 2 Sub-commands
Name
Function
NOP
No operation
PRM_RD
Reads Parameters.
PRM_WR
Writes Parameters.
ALM_RD
Reads fault and alarm.
INV_I/O
Controls Inverter I/O.