Byte
Bit 7 ... Bit 0
Default value
0
Reaction to CPU Stop
n
Bit 0: Keep last valid value
n
Bit 1: Substitute a value
n
Bit 6: reserved
n
Bit 7: reserved
00h
1
Substitute value
n
Bit 0: Substitute value "1" on channel 0
n
Bit 1: Substitute value "1" on channel 1
n
Bit 2: Substitute value "1" on channel 2
n
Bit 3: Substitute value "1" on channel 3
n
Bit 4: Substitute value "1" on channel 4
n
Bit 5: Substitute value "1" on channel 5
n
Bit 6: Substitute value "1" on channel 6
n
Bit 7: Substitute value "1" on channel 7
00h
2
not relevant
00h
3
not relevant
00h
You should only enable the parameters in byte 0, "Hold last valid value"
and "Enable substitute value" as an alternative.
Here the module reaction at CPU-STOP may be set. There are the following possibilities:
n
Keep last valid value
–
The value of each channel is frozen when the CPU is stopped
n
Substitute a value
–
At CPU-STOP each channel is substituted by a value which may be assigned by
byte 1.
4.7.2 Technical data
Order no.
322-5FF00
Type
SM 322
SPEED-Bus
-
Current consumption/power loss
Current consumption from backplane bus
100 mA
Power loss
8.6 W
Technical data digital outputs
Number of outputs
8
Cable length, shielded
1000 m
Cable length, unshielded
600 m
Reaction to CPU-Stop
VIPA System 300S
Digital Output Modules
322-5FF00 - DO 8xAC 120/230V 2A > Technical data
HB140 | SM-DIO | | en | Rev. 16-43
63