![YASKAWA VIPA IM 053IP Скачать руководство пользователя страница 90](http://html.mh-extra.com/html/yaskawa/vipa-im-053ip/vipa-im-053ip_manual_907127090.webp)
Modular device profile
Index:Sub
Name
Type
Offset
Access Default
Description
0xF000:00
Modular device
profile
U8
0
ro
4
Contains information to interpret the objects in func-
tion areas of the modules
0xF000:01
Module index dis-
tance
U16
16
ro
1
Index distance between two modules
0xF000:02
Maximum number
of modules
U16
32
ro
0x40 (64)
Maximum number of modules
0xF000:03
General configu-
ration
U32
48
ro
0
0xF000:04
General informa-
tion
U32
80
ro
0
Ä
‘Explanation of the elements’ page 71
Module Profile List
Index:Sub
Name
Type
Offset
Access
Default
Description
0xF010:00
Module Profile
List
U8
0
ro
0x40 (64)
Module ID of the modules
n
Bit 15...0: Module profile information of the
module
n
Bit 31…16: fix (0) Module profile specific infor-
mation
0xF010:01
Subindex 001
U32
16
ro
0
0xF010:02
Subindex 002
U32
48
ro
0
0xF010: ...
...
U32
...
ro
0xF010:40
Subindex 064
U32
ro
0
Ä
‘Explanation of the elements’ page 71
Configured Module Ident List
Index:Sub
Name
Type
Offset
Access Default
Description
0xF030:00
Configured
Module Ident List
U8
0
rw
0x40 (64)
Module ID of the configured modules
0xF030:01
Subindex 001
U32
16
rw
0
0xF030:02
Subindex 002
U32
48
rw
0
0xF030: ...
...
U32
...
rw
0xF030:40
Subindex 064
U32
rw
0
Ä
‘Explanation of the elements’ page 71
n
When writing to a subindex the entered value is compared with the module ID of the
same subindex of index 0xF050. So the configuration may be checked.
n
Some configuration tools cannot automatically be write to this index, thus some con-
figuration errors may not be detected.
VIPA System SLIO
Deployment
Object Dictionary
HB300 | IM | 053-1EC01 | en | 18-49