![YASKAWA VIPA IM 053IP Скачать руководство пользователя страница 76](http://html.mh-extra.com/html/yaskawa/vipa-im-053ip/vipa-im-053ip_manual_907127076.webp)
SyncManager Type
Index:Sub
Name
Type
Offset
Access Default
Description
0x1C00:00
SyncManager
Type
U8
0
ro
4
Sync Manager Communication Type
0x1C00:01
SyncManager 1
U8
16
ro
1
1: Mailbox receive (master to slave)
0x1C00:02
SyncManager 2
U8
24
ro
2
2: Mailbox send (slave to master)
0x1C00:03
SyncManager 3
U8
32
ro
3
3: Process data output
0x1C00:04
SyncManager 4
U8
40
ro
4
4: Process data input
Ä
‘Explanation of the elements’ page 71
RxPDO Assign
Index:Sub
Name
Type
Offset
Access
Default
Description
0x1C12:00
RxPDO Assign
U8
0
ro
Number of
modules
with process
output data
Sync Manager 2 PDO Assignment (0x16yy)
0x1C12:01
RxPDO Mapping
1
U16
16
ro
PDO Mapping object index of assigned PDO
0x1C12 ...
...
U16
...
ro
...
0x1C12:40
RxPDO Mapping
64
U16
ro
Ä
‘Explanation of the elements’ page 71
TxPDO Assign
Index:Sub
Name
Type
Offset
Access
Default
Description
0x1C13:00
TxPDO Assign
U8
0
ro
Number of
input PDOs
of coupler
and modules
Sync Manager 3 PDO Assignment
0x1C13:01
TxPDO Mapping
1
U16
16
ro
PDO Mapping object index of assigned PDO
(0x1Ayy)
0x1C13:02
TxPDO Mapping
2
U16
ro
0x1C13: ...
...
U16
...
ro
...
0x1C13:40
TxPDO Mapping
64
U16
ro
Ä
‘Explanation of the elements’ page 71
The EtherCAT coupler also has process input data, which show the alarm status. So
there is in the first place the assignment 0x1AFF for the input PDOs of the coupler.
VIPA System SLIO
Deployment
Object Dictionary
HB300 | IM | 053-1EC01 | en | 18-49
76