![YASKAWA VIPA IM 053IP Скачать руководство пользователя страница 53](http://html.mh-extra.com/html/yaskawa/vipa-im-053ip/vipa-im-053ip_manual_907127053.webp)
Input data EtherCAT-Slot
Index
Module
Subindex
0x6000
SM 021 DI 2x DC 24V
01h, 02h
0x6002
SM 031 AI 2x 12Bit
01h, 02h
0x6003
FM 050 1x32Bit
01h, 02h, 03h, 04h
0x6004
SM 021 DI 4x DC 24V
01h, 02h, 03h, 04h
Output data EtherCAT-Slot
Index
Module
Subindex
0x7001
SM 022 DO 4x DC 24V
01h, 02h, 03h, 04h
0x7003
FM 050 1x32Bit
01h, 02h, 03h, 04h
Read input data
Index:Sub
Name
Type
Offset
Access
Default
Description
0x6000...
0x603F:00
Input data
U8
0
ro
60
Number of subindexes of the input data for the
corresponding EtherCAT-Slot.
0x6000...
0x603F:01
U32
16
ro
Input data (see module description)
0x6000...
0x603F:02
U32
ro
0x6000...
0x603F: ...
...
...
ro
Ä
‘Explanation of the elements’ page 71
With this object the input data of a System SLIO module may be read. Here the
addressing of the EtherCAT-Slot via index ( EtherCAT-Slot) takes place. The
corresponding input data may be accessed via subindexes. The allocation of the subin-
dexes may be found in the description of the corresponding module.
VIPA System SLIO
Deployment
Accessing the System SLIO > Accessing the I/O area
HB300 | IM | 053-1EC01 | en | 18-49
53