Name
Bytes
Function
Default
DS
IX
SX
CH0A
1
C0: Input frequency track A
02h
01h
3100h
01h
CH1B
1
C0: Input frequency track B
02h
01h
3101h
02h
CH2A
1
C1: Input frequency track A
02h
01h
3102h
03h
CH3B
1
C1: Input frequency track B
02h
01h
3103h
04h
MODE2_I
1
C0: Counter mode 2
1
00h
80h
3104h
05h
MODE3_I
1
C0: Counter mode 3
1
00h
80h
3105h
06h
MODE2_II
1
C1: Counter mode 2
1
00h
82h
3106h
07h
MODE3_II
1
C1: Counter mode 3
1
00h
82h
3107h
08h
1) This parameter may only be transferred at STOP state
.
The counter is controlled via the internal gate (I gate). The I gate corresponds to the soft-
ware gate (SW gate).
SW gate:
Open (activate):
in user program by edge 0-1 SW_GATE_SET in the
control word
.
Close (deactivate):
in user program by edge 0-1 SW_GATE_RESET in the
control word
.
4.2 In-/Output area
4.2.1 Input area 12byte
At CPU, PROFIBUS and PROFINET the input area is embedded to the corresponding
address area.
IX - Index for access via CANopen
SX - Subindex for access via EtherCAT with Index 6000h + EtherCAT-Slot
More can be found in the according manual of your bus coupler.
Addr.
Name
Bytes
Function
IX
SX
+0
CV_I
4
Counter 0:
Counter value
5400h/s
01h
+4
CV_II
4
Counter 1:
Counter value
5400h/s+1
02h
+8
CSTS_I
2
Counter 0:
Counter status
5402h/s
03h
+10
CSTS_II
2
Counter 1:
Counter status
5402h/s+1
04h
The
counter value
always contains the current value of the corresponding counter.
Control counter
Input area
CV_I CV_II Counter value
VIPA System SLIO
Deployment
In-/Output area > Input area 12byte
HB300 | FM | 050-1BB30 | en | 20-40