The wiring happens without a tool.
1.
Determine according to the casing labelling the connection position.
2.
Insert through the round connection hole of the according contact your prepared
wire until it stops, so that it is fixed.
ð
By pushing the contact spring opens, thus ensuring the necessary contact pres-
sure.
The wire is to be removed by means of a screwdriver with 2.5mm blade width.
1.
Press with your screwdriver vertically at the release button.
ð
The contact spring releases the wire.
2.
Pull the wire from the round hole.
2.8 Wiring power modules
Power modules are either integrated to the head module or may be installed between the
periphery modules. With power modules, terminals with spring clamp technology are
used for wiring. The spring clamp technology allows quick and easy connection of your
signal and supply lines. In contrast to screw terminal connections this type of connection
is vibration proof.
U
max
30V DC
I
max
10A
Cross section
0.08 ... 1.5mm
2
(AWG 28 ... 16)
Stripping length 10mm
Insert wire
Remove wire
Terminal module terminals
Data
VIPA System SLIO
Basics and mounting
Wiring power modules
HB300 | FM | 050-1BB30 | en | 20-40
25