2.14 General data for the System SLIO
Conformity and approval
Conformity
CE
2014/35/EU
Low-voltage directive
2014/30/EU
EMC directive
Approval
UL
-
Refer to Technical data
Others
RoHS
2011/65/EU
Restriction of the use of certain hazardous substances in
electrical and electronic equipment
Protection of persons and device protection
Type of protection
-
IP20
Electrical isolation
to the field bus
-
electrically isolated
to the process level
-
electrically isolated
Insulation resistance
-
-
Insulation voltage to reference earth
Inputs / outputs
-
AC / DC 50V, test voltage AC 500V
Protective measures
-
against short circuit
Environmental conditions to EN 61131-2
Climatic
Storage / transport
EN 60068-2-14
-25…+70°C
Operation
Horizontal installation hanging
EN 61131-2
0…+60°C
Horizontal installation lying
EN 61131-2
0…+55°C
Vertical installation
EN 61131-2
0…+50°C
Air humidity
EN 60068-2-30
RH1 (without condensation, rel. humidity 10…95%)
Pollution
EN 61131-2
Degree of pollution 2
Installation altitude max.
-
2000m
Mechanical
Oscillation
EN 60068-2-6
1g, 9Hz ... 150Hz
Shock
EN 60068-2-27
15g, 11ms
VIPA System SLIO
Basics and mounting
General data for the System SLIO
HB300 | FM | 050-1BB30 | en | 20-40
39