4.5 Diagnostics and interrupt
Via the parameterization you may activate a diagnostic interrupt for the module. With a
diagnostic interrupt the module serves for diagnostic data for diagnostic interrupt
incoming
.
As soon as the reason for releasing a diagnostic interrupt is no longer present, the diag-
nostic interrupt
going
automatically takes place. Within this time window (1. diagnostic inter-
rupt
incoming
until last diagnostic interrupt
going
) the MF-LED of the module is on.
Event
Process
interrupt
Diagnostics
interrupt
parameterizable
Encoder power supply is missing
1
-
X
X
1) The module may only send a diagnostic interrupt in case of missing encoder power supply, if this received its parameters before. If the encoder power supply is already missing
during startup, the module does not send an diagnostic interrupt!
DS - Record set for access via CPU, PROFIBUS and PROFINET. The access happens
by DS 01h. Additionally the first 4 bytes may be accessed by DS 00h.
IX - Index for access via CANopen. The access happens by IX 2F01h. Additionally the
first 4 bytes may be accessed by IX 2F00h.
SX - Subindex for access via EtherCAT with Index 5005h.
More can be found in the according manual of your bus coupler.
Name
Bytes
Function
Default
DS
IX
SX
ERR_A
1
Diagnostic
00h
01h
2F01h
02h
MODTYP
1
Module information
18h
03h
ERR_C
1
reserved
00h
04h
ERR_D
1
reserved
00h
05h
CHTYP
1
Channel type
76h
06h
NUMBIT
1
Number diagnostics bits per channel
08h
07h
NUMCH
1
Number channels of the module
01h
08h
CHERR
1
reserved
00h
09h
CH0ERR…
CH7ERR
8
reserved
00h
0Ah ... 11h
DIAG_US
4
µs ticker
00h
13h
Byte
Bit 7 ... 0
0
n
Bit 0: set at module failure
n
Bit 1: set at internal error
n
Bit 2: set at external error
n
Bit 3: set at channel error
n
Bit 4: set at missing encoder power supply
n
Bit 7 ... 5: reserved
Overview
Diagnostic data
ERR_A Diagnostic
VIPA System SLIO
Deployment
Diagnostics and interrupt
HB300 | FM | 050-1BS00 | en | 20-40