For wires with a core cross-section of 0.08mm
2
up to 1.5mm
2
.
Pos.
Function
Type
Description
1
---
---
not connected
2
DC 24V
I
DC 24V for power section supply
3
0V
I
GND for power section supply
4
Sys DC 24V
I
DC 24V for electronic section supply
5
---
---
not connected
6
DC 24V
I
DC 24V for power section supply
7
0V
I
GND for power section supply
8
Sys 0V
I
GND for electronic section supply
I: Input
CAUTION!
Since the power section supply is not internally protected, it is to be exter-
nally protected with a fuse, which corresponds to the maximum current.
This means max. 10A is to be protected by a 10A fuse (fast) respectively
by a line circuit breaker 10A characteristics Z!
The electronic power section supply is internally protected against higher
voltage by fuse. The fuse is within the power module. If the fuse releases,
its electronic module must be exchanged!
n
The power section supply is to be externally protected with a fuse, which corresponds
to the maximum current. This means max. 10A is to be protected with a 10A fuse
(fast) respectively by a line circuit breaker 10A characteristics Z!
n
It is recommended to externally protect the electronic power supply for head modules
and I/O area with a 2A fuse (fast) respectively by a line circuit breaker 2A characteris-
tics Z.
n
The electronic power supply for the I/O area of the power module 007-1AB10 should
also be externally protected with a 1A fuse (fast) respectively by a line circuit breaker
1A characteristics Z.
After PowerON of the System SLIO the LEDs RUN respectively MF get on so far as the
sum current does not exceed 3A. With a sum current greater than 3A the LEDs may not
be activated. Here the power module with the order number 007-1AB10 is to be placed
between the peripheral modules.
PM - Power module
Fusing
State of the electronic
power supply via LEDs
VIPA System SLIO
Basics and mounting
Wiring power modules
HB300 | FM | 050-1BS00 | en | 20-40