56
Table 4.6 “C” Parameters
Access Level
Name
Address
Description
Data
Range
Unit
Default
During
Run
V/f
V/f
w/PG
OLV
FV
OLV2
C1-01
0200h
Accel Time 1
0.0 ~ 6000.0 Sec
0.1 Sec
10.0 Sec
R
Q
Q
Q
Q
Q
C1-02
0201h
Decel Time 1
0.0 ~ 6000.0 Sec
0.1 Sec
10.0 Sec
R
Q
Q
Q
Q
Q
C1-03
0202h
Accel Time 2
0.0 ~ 6000.0 Sec
0.1 Sec
10.0 Sec
R
A
A
A
A
A
C1-04
0203h
Decel Time 2
0.0 ~ 6000.0 Sec
0.1 Sec
10.0 Sec
R
A
A
A
A
A
C1-05
0204h
Accel Time 3
0.0 ~ 6000.0 Sec
0.1 Sec
10.0 Sec
A
A
A
A
A
C1-06
0205h
Decel Time 3
0.0 ~ 6000.0 Sec
0.1 Sec
10.0 Sec
A
A
A
A
A
C1-07
0206h
Accel Time 4
0.0 ~ 6000.0 Sec
0.1 Sec
10.0 Sec
A
A
A
A
A
C1-08
0207h
Decel Time 4
0.0 ~ 6000.0 Sec
0.1 Sec
10.0 Sec
A
A
A
A
A
C1-09
0208h
Fast Stop Time
0.0 ~ 6000.0 Sec
0.1 Sec
10.0 Sec
A
A
A
A
A
0 0.01
Seconds
C1-10
0209h Accel/Decel
Units
1 0.1
Seconds
1
1
A A A A A
C1-11
020Ah
Accel/Decel Switchover
Frequency
0.0 ~ 400.0 Hz
0.1 Hz
0.0 Hz
A
A
A
A
A
C2-01
020Bh
S-Curve at Accel Start
0.0 ~ 2.5 Sec
0.01 Sec
0.20 Sec
A
A
A
A
A
C2-02
020Ch
S-Curve at Accel End
0.0 ~ 2.5 Sec
0.01 Sec
0.20 Sec
A
A
A
A
A
C2-03
020Dh
S-Curve at Decel Start
0.0 ~ 2.5 Sec
0.01 Sec
0.20 Sec
A
A
A
A
A
C2-04
020Eh
S-Curve at Decel End
0.0 ~ 2.5 Sec
0.01 Sec
0.00 Sec
A
A
A
A
A
C3-01
020Fh
Slip Compensation Gain
0.0 ~ 2.5
0.1
Cntrl Meth
R A A A A
C3-02
0210h
Slip Compensation Filter Time
0 ~ 10000 ms
1 ms
Cntrl Meth
A A
C3-03
0211h
Slip Compensation Limit
0 ~ 250 %
1 %
200 %
A
A
0 Disabled
C3-04
0212h
Slip Compensation During
Regeneration
1 Enabled
1
0
A A
0 Disabled
C3-05
0213h
Output Voltage Limit Selection
1 Enabled
1 0
A
A
A
C4-01
0215h
Torque Compensation Gain
0.0 ~ 2.5
0.01
1.00
R
A
A
A
C4-02
0216h
Torque Compensation Filter
Time
0 ~ 10000 ms
1 ms
Cntrl Meth
A A A
C4-03
0217h
Forward Direction Torque
Compensation at Start
0.0 ~ 200.0 %
0.1 %
0.0 %
A
C4-04
0218h
Reverse Direction Torque
Compensation at Start
-200.0 ~ 0.0 %
0.1 %
0.0 %
A
C4-05
0219h
Torque Compensation at Start
Filter Time
0 ~ 200 ms
1 ms
10 ms
A
C5-01
021Bh
ASR Proportional Gain 1
Cntrl Meth
0.01
Cntrl Meth
R A A A
C5-02
021Ch
ASR Integral Time 1
0.000 ~ 10.000 Sec
0.001 Sec
Cntrl Meth
R A A A
C5-03
021Dh
ASR Proportional Gain 2
Cntrl Meth
0.01
Cntrl Meth
R A A A
C5-04
021Eh
ASR Integral Time 2
0.000 ~ 10.000 Sec
0.001 Sec
Cntrl Meth
R A A A
C5-05
021Fh
ASR Limit
0.0 ~ 20.0 %
0.1 %
0.0 %
A
C5-06
0220h ASR
Filter Time
0.000 ~ 0.500 Sec
0.001 Sec
Cntrl Meth
A
A
C5-07
0221h
ASR Gain Switchover
Frequency
0.0 ~ 400.0 Hz
0.1 Hz
0.0 Hz
A
A
C5-08
0222h
ASR Integral Limit
0 ~ 400 %
1 %
400 %
A
A
C5-10
0231h ASR
Filter Time 2
0.000 ~ 0.500 Sec
0.001 Sec
0.010 Sec
A
1h Fc=2.0kHz
2h Fc=5.0kHz
3h Fc=8.0kHz
4h Fc=10.0kHz
5h Fc=12.5kHz
6h Fc=15.0kHz
C6-02
0224h Carrier
Frequency
Selection
Fh
C6-03 ~ C6-05
1 kVA
Dep.
Q Q Q Q Q
C6-03
0225h Carrier
Frequency
Maximum
0.4 ~ 15.0 kHz
(kVA Dependent)
0.1 kHz
kVA Dep.
A A A A
C6-04
0226h Carrier
Frequency
Minimum
0.4 ~ 15.0 kHz
(kVA Dependent)
0.1 kHz
kVA Dep.
A A
C6-05
0227h
Carrier Frequency Gain
0 ~ 99
1
0
A
A
Содержание Varispeed G7
Страница 1: ...Modbus Communication Manual G7 Drive Drive Model CIMR G7U Document Number TM G7 11...
Страница 2: ...2 Page intentionally blank...
Страница 6: ...6 Notes...
Страница 10: ...10 G7 Drive Connections Figure 1 2 G7 Drive Connections...
Страница 18: ...18 Notes...
Страница 32: ...32 Notes...
Страница 80: ...80 Notes...
Страница 82: ...82 Notes drive drive Name Date...