13
Communication Parameters
The following communications parameters affect communication over RS-232, RS-422 and RS-485 networks. The RS-232 communication
parameters are fixed. In addition, the node address is ignored when communicating via RS-232.
H5 group communication parameters can only be changed via the drive keypad.
Note: Drive power must be cycled for changes to H5 Group parameters to be recognized.
RS-232 Communication
The RS-232 communications parameters are fixed at the values shown below. Although the node address is ignored, the master when
communicating to the G7 drive in this method typically uses a node address of 1.
Table 1.1 RS-232 (RJ-45 port) Communication Parameters
Value
Description
Baud rate
9600
Parity None
Stop Bits
1
Node Address
N/A
RS-422/RS-485 Communication
Node Address – H5-01
. The node address is set through G7 drive parameter H5-01. When communicating via RS-422 or RS-485, a
unique node address between 0 and 20h (32 decimal), inclusive, must be entered. The default G7 drive address is 1Fh (31 decimal).
The address is always entered as a hexadecimal number (refer to the conversion chart in Chapter 4). Address 0 is typically reserved for
global messages.
Baud Rate – H5-02
. Select the baud rate that matches the controller’s communication configuration.
Table 1.2 Baud Rate – Parameter H5-02
Value
Description
0 1200bps
1 2400bps
2 4800bps
3
9600bps (Default Setting)
4 19,200bps
Parity – H5-03
. Select the parity that matches the controller’s communication configuration.
Table 1.3 Parity – Parameter H5-03
Value
Description
0
None (Default Setting)
1 Even
2 Odd
Содержание Varispeed G7
Страница 1: ...Modbus Communication Manual G7 Drive Drive Model CIMR G7U Document Number TM G7 11...
Страница 2: ...2 Page intentionally blank...
Страница 6: ...6 Notes...
Страница 10: ...10 G7 Drive Connections Figure 1 2 G7 Drive Connections...
Страница 18: ...18 Notes...
Страница 32: ...32 Notes...
Страница 80: ...80 Notes...
Страница 82: ...82 Notes drive drive Name Date...