8
Mounting to a Gasketed Cabinet (Internal Sink)
The standard enclosure (with the heatsink
mounted internally) can be easily changed to
an externally mounted heatsink arrangement,
but the enclosure's mounting face must be
gasketed.
VS
−
656RC5 Heat Loss
Model CIMR−R5A
43P7
3.7
6
30
50
80
45P5
5.5
9
40
60
100
47P5
7.5
13
60
60
120
4011
11
19
80
70
150
4015
15
26
110
90
200
4018
18.5
32
120
100
220
4022
22
37
140
110
250
4030
30
51
210
140
350
4037
37
64
290
160
450
4045
45
77
360
190
550
4055
55
96
470
260
730
4075
75
128
550
310
860
Fin
Inside Unit
Total Heat Loss
Rated Capacity
Rated Current
Fin Cooling
Fan cooled
kW
A
400 V Class
Model CIMR−R5A
23P7
3.7
13
70
60
130
25P5
5.5
19
70
60
130
27P5
7.5
26
90
80
170
2011
11
37
160
110
270
2015
15
51
200
130
330
2018
18.5
64
250
150
400
2022
22
77
320
180
500
2030
30
102
410
220
630
2037
37
126
540
290
830
Fin
Inside Unit
Total Heat Loss
Rated Capacity
Rated Current
Fin Cooling
Fan cooled
kW
A
200 V Class
Heat Loss W
*
Heat Loss W
*
* Values are the regenerative torque at 80 % continuous rating.
* Values are the regenerative torque at 80 % continuous rating.
UPPER COVER
HEATSINK
LOWER COVER
COVER MTG SCREW
55 ℃
45 ℃
UPPER COVER
INTERNAL HEATSINK
UPPER PART AIR TEMPERATURE
−10 TO 55 ℃
OPEN CHASSIS
TYPE POWER
REGENERATIVE UNIT
INLET AIR
TEMPERATURE
−10 TO 45 ℃
PERIPHERAL
TEMPERATURE
40 ℃
LOWER COVER
HEATSINK
Remove the uppper and lower covers for the models
of 30 kW or less in 200 V and 400V classes.