Applications of the VS-656RC5

Selection

■Use 1:1 with an inverter. Do not connect more than one inverter to one VS-656RC5.

■Use a VS-656RC5 whose capacity is equal to one exceeding the capacity of the inverter to be connected.

■Do not connect the VS-656RC5 in parallel with another power regenerative unit.

■When power regeneration is executed continuously using ○

+ 3 terminal of the VS-686SS5,

set the maximum to 80%. If more regeneration is necessary, use a larger capacity VS-656RC5 

sand inverter.

Installation

■Avoid oil mist or dust. Place the inverter in a clean area or house it in a totally-enclosed case so that no

contamination enters.To use the totally-enclosed case, select the cooling method and panel dimensions so the

VS-656RC5 ambient temperature will be within the allowable range.

■Do not install the VS-656RC5 on flammable material, such as wood.

■Install the VS-656RC5 on a wall with the longer side in the vertical position.

■Do not subject the inverter to halogen gases, such as fluorine, chlorine, bromine, and iodine, at any time

even during transportation or installation.

Operation

■Applying power to the VS-656RC5, DOUBLE CHECK WIRING AND SEQUENCE BEFORE TURNING THE

POWER ON.

■After turning the power of the VS-656RC5 OFF, electric charges in the internal capacitors are retained

temporarily.Wait until the change LED goes off before touching the inside of the VS-656RC5.

■Use round pressure terminal when wiring UL and c-UL listed VS-656RC5. Caulking shoud be done by the

caulking tools specified by terminal manufactures.

■The VS-656RC5 cannot be used with a single-phase power supply. Make sure to use a three-phase power   

supply.

Applications of the Peripheral Devices

■Installation and selection of an AC reactor

An input three-phase reactor corresponding to each model is necessary when operating the VS-656RC5.

For selection of a reactor, see p.10 and 11. This input AC reactor is effective against saturated currents 

and excessive heat.

■Installation and selection of fuses

Connect a fuse on the primary side of the power suppressing reactor. For selection of a fuse, see p.12.

■Installation of a noise filter

When adding an input noise filter to the inverter, connect it to the primary side of the power coordinating

reactor.

Содержание VARISPEED-656RC5

Страница 1: ...T I F IED M A N A GEMENT SY S T E M JQA EM0498 QUALITY SYSTEM C ERT I F IED M A N A GEMENT SY S T E M JQA 0422 Certified for ISO9001 and ISO14001 VARISPEED 656RC5 200V CLASS 3 7 to 37kW 400V CLASS 3 7...

Страница 2: ...Torque Power Operating Conditions 5000h year Electrical costs 0 12 kWh Electric Power Consumption P 55 5kW 2 33 3kW 15 11 1 2 3 7kW 2 25 9kW 5 48 1 2 0 9 0 95 8 49kW 4 82kW 3 67kW Electrical Costs 3...

Страница 3: ...tage Fluctuation Allowable Frequency Fluctuation Imbalance Rate between Phases 380 to 460 VAC 50 60 Hz 15 to 10 3 Hz 300 ms Free phase rotation Within 2 150 for 30 sec 100 for 1 min 25 ED 80 continuou...

Страница 4: ...AC MB MC Notes 1 Make sure to use the specified reactor fuse and fuse holder 2 Remove the wiring of terminals r l1 and s l2 since they were connected at the factory 3 Connect Varispeed G7 AC power sup...

Страница 5: ...n Circuit Terminal Functions Type No Signal Function Signal Level Sequence Input S1 S2 S3 S4 SC SS SP M1 M2 M3 M4 MA MC MB MC AM AC Photocoupler Output Relay Output Multi functional Analog Output MANU...

Страница 6: ...66 7 0 325 450 285 275 435 7 5 23 27 M6 330 610 285 275 435 87 5 200 300 205 186 285 8 0 6 6 M6 200 300 205 186 285 8 0 250 380 225 236 365 7 5 11 11 M6 250 380 225 236 365 7 5 140 280 180 126 266 7 0...

Страница 7: ...W A 400 V Class Model CIMR R5A 23P7 3 7 13 70 60 130 25P5 5 5 19 70 60 130 27P5 7 5 26 90 80 170 2011 11 37 160 110 270 2015 15 51 200 130 330 2018 18 5 64 250 150 400 2022 22 77 320 180 500 2030 30 1...

Страница 8: ...n level during a run 200 V class approx 150 VAC or less 400 V class approx 300 VAC or less Baseblock Circuit Error EEPROM Error CPU Internal A D Converter Error LED Display RUN DS1 DS2 Meaning Content...

Страница 9: ...80 80 80 95 50 50 50 75 75 75 75 75 75 114 119 139 147 5 155 150 155 170 182 8 X002491 X002492 X002493 X002495 X002497 X002498 X002555 X002556 X002557 2 200 V Class VS 656RC5 CIMR R5A Current Value A...

Страница 10: ...4015 4018 4022 4030 4037 4045 4055 4075 7 5 7 5 10 15 25 25 30 40 50 60 75 100 1 2 1 2 0 6 0 4 0 3 0 3 0 2 0 15 0 12 0 1 0 08 0 06 85 85 85 85 105 105 105 105 130 130 160 160 61 61 61 61 71 71 71 71 8...

Страница 11: ...7 45P5 47P5 4011 4015 4018 4022 4030 4037 4045 4055 4075 CR6L 20 UL CR6L 100 UL CR6L 150 UL CMS 4 CMS 5 FU002091 FU002092 3 4 3 3 CR6L 30 UL CR6L 50 UL CR6L 75 UL FU002087 FU000927 FU000928 FU002088 F...

Страница 12: ...T GASKET GASKET GASKET GASKET 2 5 DIA HOLES 4 M5 SCREWS 4 8 DIA HOLES C 4 8 DIA HOLES C 2 4 8 DIA HOLES D 25 25 61 610 8 309 4 5 C DC 25 300 325 12 5 7 5 19 5 27 12 5 4 5 571 625 187 61 C C C D 4 4 C...

Страница 13: ...Digital Operator Extension Cable LED Monitor Digital Operator LED Monitor Model JVOP 139 Digital Operator Model JVOP 130 LED Monitor Digital Operator Extension Cable Panel Cutout Viewed from the fron...

Страница 14: ...e and iodine at any time even during transportation or installation Operation Applying power to the VS 656RC5 DOUBLE CHECK WIRING AND SEQUENCE BEFORE TURNING THE POWER ON After turning the power of th...

Страница 15: ...SHANGHAI CO LTD No 18 Xizang Zhong Road Room 1702 1707 Harbour Ring Plaza Shanghai 200001 China Phone 86 21 5385 2200 Fax 86 21 5385 3299 YASKAWA ELECTRIC SHANGHAI CO LTD BEIJING OFFICE Room 1011A Tow...

Отзывы: