8
5
Related constants for 2C-Relay Output Card DO-02C
Table
2
Related constants for 2C-Relay Output Card DO-02C
Operator
function
display
Operator
display
Constant
No.
Name
Setting
range
Factory
setting
Change
during
operation
Reference
DO 02
DO-02
Ch1 Select
F5-01
Channel 1 output
selection
0 to FF
0
Disabled
S
Refer to Table 3 for the output func-
tion.
S
Refer to the function selection of the
DO-02
DO-02
Ch2 Select
F5-02
Channel 2 output
selection
0 to FF
1
Disabled
S
Refer to the function selection of the
multi-function output terminal of the
inverter for details of each function.
Table
3
Multi-function Output Functions of DC-02C
Setting
value
Function
Setting
value
Function
00
During run (ON: run command is input or during in-
verter output)
20
−
01
Zero speed
21
−
02
Frequency agree 1
22
−
03
Desired frequency agree 1
23
−
04
Frequency detection 1
24
−
05
Frequency detection 2
25
−
06
Inverter Operation ready
26
−
07
During undervoltage (UV) detection
27
−
08
During baseblock (NO contact output)
28
−
09
Frequency reference mode
29
−
0A
Run command mode
2A
−
0B
Overtorque detection 1 (NO contact output)
2B
−
0C
Loss of frequency reference
2C
−
0D
Braking resistor fault
2D
−
0E
Fault (Faults other than CPF00 or CPF01)
2E
−
0F
−
2F
−
10
Alarm
30
During torque limit *
2
11
Fault reset command active
31
During speed limit *
1
12
Timer function output
32
−
13
Frequency agree 2
33
During zero-servo *
1
14
Desired frequency agree 2
34
−
15
Frequency detection 3
35
−
16
Frequency detection 4
36
−
17
Overtorque detection 1 (NC contact output)
37
During run 2 (Other than Base block, DC injection
braking, initial excitation)
18
Overtorque detection 2 (NO contact output)
38
−
19
Overtorque detection 2 (NC contact output)
39
−
1A
During reverse run
3A
−
1B
During baseblock (NC contact output)
3B
−
1C
−
3C
−
1D
Regenerating/motoring mode (Closed during regener-
ating mode) *
1
3D
−
1E
Restart enabled
3E
−
1F
Motor overload (OL1) pre-alarm
3F
−
* 1. Can be used during Flux vector control mode.
* 2. Can be used during Open loop vector or Flux vector control mode.