9
Table
4
C
onstants
List
Digital
Operator
Digital
Operator
Con-
Setting
Factory
Change durin
g
Control
Method
(
f
=Setting
enable
×
=Setting
disable)
Digital
Operator
Function
Display
Digital
Operator
Display
Con
-
stant No.
Constant
Name
Setting Range
Factory Setting
during
Operation
(
f
=Enable,
×
=Disable)
Data
Selection
V/f Con- trol
V/f with PG Feed- back
Open Loop V
ec- tor
Flux Vec- tor
Reference
Source
B1
−
01
Reference
selection
0t
o
3
1
×
0
:
Digital
operator
1
:
Terminal
2
:
Serial
communication
3
:
Option
PCB
f
f
f
f
Sequence
R
un
Source
B1
−
02
Operation
method
selection
0t
o
3
1
×
0
:
Digital
operator
1
:
Terminal
2
:
Serial
communication
3
:
Option
PCB
f
f
f
f
Stopping
method
B1
−
03
Stopping
method
selection
0t
o
3
0
×
0
:
Ramp
to
Stop
1
:
Coast
to
Stop
2
:
D
C
injection
to
stop
3
:
Coast
with
timer
f
f
f
f
Reverse
Oper
B1
−
04
Prohibition
of
reverse
operation
0,
1
0
×
0
:
Reverse
enabled
1
:
Reverse
disabled
f
f
f
f
AI-14B
AI-14
Input
Set
F2-01
Bi-polar
or
uni-polar
inputselection
0/1
0
×
0
:
0
to
10V
1:
−
10
to
10
V
×
f
×
f
DI-08,
DI-16H2
DI
Input
F3-01
Digital
input
option
0t
o
8
1
×
0
:
BCD
1%
1
:
B
C
D
0.1%
2
:
B
C
D
0.01%
3
:
BCD
1
Hz
4
:
BCD
0.1Hz
5
:
BCD
0.01Hz
6
B
C
D
(5
digits)
input
7
:
Binary
100%=255
4095/10000
×
f
×
f
AO
Ch1
Select
F4-01
Channel
1
monitor
selection
1t
o
31
2
×
0
:
Disabled
1
:
Enabled
×
f
×
×
AO-08,
-12
AO
C
h1
Gain
F4
−
02
Channel
1
gain
0
to
2.50
1.00
f
×
f
×
f
AO
08,
12
AO
Ch2
Select
F4
−
03
Channel
2
monitor
selection
1t
o
31
3
×
×
f
×
f
AO
C
h2
Gain
F4
−
04
Channel
2
gain
0
to
2.50
1.00
f
×
f
×
f
DO
02C
DO-02
Ch1
Select
F5
−
01
Channel
1
output
selestion
0t
o
FF
0
×
×
f
×
f
DO-02C
DO-02
Ch2
Select
F5
−
02
Channel
2
output
selestion
0t
o
FF
1
×
×
f
×
×
DO-08
DO-08
Selection
F6
−
01
Output
mode
selection
0t
o
2
0
×
0
:
8-channel
individual
1
:
Binary
output
×
f
×
×
DO-36F
PO-36F
Selection
F7
−
01
Frequency
multiple
selection
0t
o
4
0
×
0
:
1F
3
:
12F
1
:
6F
4
:
36F
2:
10F
×
f
×
×