5.7 H: Terminal Functions
276
YASKAWA ELECTRIC
SIEP C710636 02B YASKAWA U1000 Technical Manual
◆
H2: Multi-Function Digital Outputs
■
H2-01 to H2-03: Multi-Function Digital Outputs Function Selection
The drive has three multi-function output terminals.
lists the functions available for theses terminals using
H2-01, H2-02, and H2-03.
Table 5.40 Multi-Function Digital Output Terminal Settings
Setting 0: During Run
Output closes when the drive is outputting a voltage.
Figure 5.66
Figure 5.66 During Run Time Chart
No.
Parameter Name
Setting Range
Default
CIMR-UA
, CIMR-UD
, CIMR-UT
CIMR-UB
H2-01
Terminal M1-M2 Function Selection (relay)
Terminal M1-M2 Function Selection
0 to 192
0: During run
H2-02
Terminal P1-PC Function Selection (open-collector)
Terminal M3-M4 Function Selection
0 to 192
1: Zero Speed
H2-03
Terminal P2-PC Function Selection (open-collector)
Terminal M5-M6 Function Selection
0 to 192
2: Speed agree 1
Setting
Function
Page
Setting
Function
Page
0
During run
1E
Restart enabled
1
Zero Speed
1F
Motor overload alarm (oL1)
2
Speed agree 1
20
Drive overheat pre-alarm (oH)
3
User-set speed agree 1
22
Mechanical Weakening detection
4
Frequency detection 1
2F
Maintenance period
5
Frequency detection 2
30
During torque limit
6
Drive ready
31
During speed limit
7
During Power Supply Voltage Fault
32
During speed limit in Torque Control
8
During baseblock (N.O.)
33
Zero Servo complete
9
Frequency reference source
37
During frequency output
A
Run command source
38
Drive enabled
B
Torque detection 1 (N.O.)
39
Power consumption pulse output
C
Frequency reference loss
3A
Regenerated power pulse output
E
Fault
3C
LOCAL/REMOTE Status
F
Through mode
3D
During Speed Search
10
Minor fault
3E
PID feedback low
11
Fault reset command active
3F
PID feedback high
12
Timer output
4C
During Fast Stop
13
Speed agree 2
4D
oH pre-alarm time limit
14
User-set speed agree 2
60
Internal cooling fan alarm
15
Frequency detection 3
61
Rotor Position Detection Complete
16
Frequency detection 4
62
Memobus Regs1 (It selects it with H2-07 and H2-08.)
17
Torque detection 1 (N.C.)
63
Memobus Regs2 (It selects it with H2-09 and H2-10.)
18
Torque detection 2 (N.O.)
64
During commercial power operation
19
Torque detection 2 (N.C.)
90
DriveWorksEZ digital output 1
1A
During reverse
91
DriveWorksEZ digital output 2
1B
During baseblock (N.C.)
92
DriveWorksEZ digital output 3
1C
Motor 2 selection
100 to 192
Functions 0 to 92 with inverse output
1D
During regeneration
–
–
–
Status
Description
Open
Drive is stopped.
Closed
A Run command is input or the drive is during deceleration or during DC injection.
ON
ON
OFF
OFF
ON
OFF
Run command
Baseblock
command
Output
frequency
During Run
SIEP_C710636_02B_1_0.book 276 ページ 2015年11月25日 水曜日 午後4時56分