![YASKAWA U1000 Series Скачать руководство пользователя страница 281](http://html.mh-extra.com/html/yaskawa/u1000-series/u1000-series_technical-manual_907114281.webp)
5.7 H: Terminal Functions
YASKAWA ELECTRIC
SIEP C710636 02B YASKAWA U1000 Technical Manual
281
5
Setting 14: User-set speed agree 2 (f
ref
/f
set
agree 2)
Closes whenever the actual output frequency or motor speed (CLV, CLV/PM) and the frequency reference are within the
speed agreement detection width (L4-04) of the speed agreement detection level (L4-03). As the detection level L4-03 is
a signed value, detection works in the specified direction only.
Figure 5.73
Figure 5.73 User Set Speed Agree 2 Example with a Positive L3-04 Value
Refer to L4-03, L4-04: Speed Agreement Detection Level and Detection Width (+/-) on page 308
for more details.
Setting 15: Frequency detection 3
Output opens when the output frequency or motor speed (CLV, CLV/PM) rises above the detection level set in L4-03 plus
the detection with set in L4-04. The terminal remains open until the output frequency or motor speed falls below the level
set in L4-03. As the detection level L4-03 is a signed value, the detection works in the specified direction only.
Figure 5.74
Figure 5.74 Frequency Detection 3 Example with a Positive L3-04 Value
Refer to L4-03, L4-04: Speed Agreement Detection Level and Detection Width (+/-) on page 308
for more details.
Status
Description
Open
Output frequency or motor speed and frequency reference are both outside the range of L4-03 ±L4-04
Closed
Output frequency or motor speed and the frequency reference are both with in the range of L4-03 ±L4-04
Status
Description
Open
Output frequency or motor speed exceeded L4-03 plus L4-04.
Closed
Output frequency or motor speed is below L4-03 or has not exceeded L4-03 plus L4-04 yet.
<1> This is the time chart when L4-07 (Speed Agree Detection Selection) is set to 1 (detection always enabled). The default
setting for L4-07 is 0 (no detection during baseblock). When L4-07 = 0, the terminal opens during baseblock.
Frequency reference
+
L4-04
Frequency reference
– L4-04
L4-03
L4-03
+
L4-04
L4-03
– L4-04
Frequency reference
0 Hz
OFF
OFF
ON
ON
Frequency reference
During
Forward
Output frequency
Output frequency
User Set
Speed Agree 2
L4-04
Frequency
detection 3
<1>
ON
OFF
L4-03
Output Frequency or
Motor Speed
SIEP_C710636_02B_1_0.book 281 ページ 2015年11月25日 水曜日 午後4時56分