5.7 H: Terminal Functions
284
YASKAWA ELECTRIC
SIEP C710636 02B YASKAWA U1000 Technical Manual
Figure 5.77
Figure 5.77 During Frequency Output Time Chart
Setting 38: Drive enable
A digital output set for “Drive enable” will reflect the status of a digital input configured as a “Drive enable” input
(H1-
= 6A). If that digital input closes, then the digital output set for “Drive enable” will also close.
Setting 39: Power consumption pulse output
Outputs a pulse to indicate the power consumption.
Refer to H2-06: Power Consumption Output Unit Selection on
for details.
Setting 3A: Regenerated power pulse output
Outputs a pulse to indicate the regenerated power.
Refer to H2-06: Power Consumption Output Unit Selection on
for details.
Setting 3C: LOCAL/REMOTE status
Output terminal closes while the drive is set for LOCAL and opens when in REMOTE.
Setting 3D: During Speed Search
Output terminal closes while Speed Search is being performed.
Refer to b3: Speed Search on page 192
for details.
Setting 3E: PID feedback low
Output terminal closes when a PID feedback loss (FbL) is detected. The feedback is considered to be lost if it falls below
the level set to b5-13 for longer than the time set to b5-14.
Refer to PID Feedback Loss Detection on page 207
details.
Setting 3F: PID feedback high
Output terminal closes when an excessive PID feedback (FbH) is detected. The feedback is considered to be lost if it rises
beyond the level set to b5-36 for longer than the time set to b5-37.
Refer to PID Feedback Loss Detection on page 207
for details.
Setting 4C: During Fast Stop
Output terminal closes when a Fast Stop is being executed.
Setting 15, 17: Fast Stop (N.O., N.C.) on page 270
.
Setting 4D: oH pre-alarm time limit
Output terminal closes when the drive is reducing the speed due to a drive overheat alarm (L8-03 = 4) and the overheat
alarm has not disappeared after ten frequency reduction operation cycles.
Refer to L8-03: Overheat Pre-Alarm
Operation Selection on page 315
for a more detailed description.
Setting 60: Internal cooling fan alarm
Output closes when the drive’s internal cooling fan has failed.
Setting 61: Rotor position detection complete
After the Run command is given, the output terminal signals that the drive has detected the rotor position (PM motors).
Status
Description
Open
REMOTE: The external reference that has been selected (either b1-01 and b1-02 or b1-15 and b1-16) is used as frequency reference and Run command source
Closed
LOCAL: The digital operator is used as frequency reference and Run command source
ON
ON
OFF
OFF
ON
OFF
ON
run command
baseblock
command
output
frequency
during run
during frequency
output
OFF