5.7 H: Terminal Functions
YASKAWA ELECTRIC
SIEP C710636 02B YASKAWA U1000 Technical Manual
279
5
Figure 5.71
Figure 5.71 Frequency Detection 2 Time Chart
Refer to L4-01, L4-02: Speed Agreement Detection Level and Detection Width on page 308
Setting 6: Drive ready
Output closes whenever the drive is ready to operate the motor. The terminal will not close under the conditions listed
below, and any Run commands will be disregarded.
• When the power is shut off
• During a fault
• When the drive’s internal power supply has malfunctioned
• When a parameter setting error makes it impossible to run
• Although stopped, an undervoltage situation occurs
• While editing a parameter in the Programming Mode (when b1-08 = 0)
Setting 7: During Power Supply Voltage Fault
Output closes when the power supply voltage or the control circuit voltage falls below the drive operating voltage or
when the power supply frequency is incorrect.
Setting 8: During baseblock (N.O.)
Output closes to indicate that the drive is in a baseblock state. While in baseblock, output transistors do not switch and no
main circuit voltage is output.
Setting 9: Frequency reference source
A digital output programmed for this function shows the frequency reference source that is currently selected.
Setting A: Run command source
A digital output programmed for this function shows the Run command source that is currently selected.
Setting B, 17, 18, 19: Torque detection 1 (N.O., N.C.), Torque detection 2 (N.O., N.C.)
These digital output functions can be used to signal an overtorque or undertorque situation to an external device.
Set up the torque detection levels and select the output function from the table below.
Refer to L6: Torque Detection on
for details.
Status
Description
Open
Normal
Closed
One of the following faults will occur: AUv (Power Supply Undervoltage), Uv (Undervoltage). or Fdv (Power Supply Frequency Fault).
Status
Description
Open
Drive is not in a baseblock state.
Closed
Baseblock is being executed.
Status
Description
Open
Frequency reference is provided from External reference 1 (b1-01) or External reference 2 (b1-15)
Closed
Frequency reference is being sourced from the digital operator.
Status
Description
Open
Run command is provided from External reference 1 (b1-02) or 2 (b1-16).
Closed
Run command is being sourced from the digital operator.
L4-02
Frequency
Detection 2
ON
OFF
L4-02
L4-01
L4-01
Output Frequency or
Motor Speed