5 Installation Procedure
YASKAWA ELECTRIC
TOBP C730600 86F YASKAWA AC Drive Option SI-T3 Installation Manual
31
u
MECHATROLINK-II Communications Cables
Connect the MECHATROLINK-II communications cable to option communication
connector CN3. Use only the following MECHATROLINK-II dedicated communications
cable.
Recommended communication cable: JEPMC-W6002-
-E
JEPMC-W6003-
Connect the terminator (model No.: JEPMC-W6022-E) on the end of the communication
lines.
Note:
Maximum transmission distance is 50 m (1969.0 in). Minimum wiring distance between stations
is 0.5 m (19.7 in).
n
Option Connection Diagram
Figure 18 Option Connection Diagram
<1>
is the length (m).
<1> Connect the provided ground wire for installations on 1000-series drives and GA500 drives. The ground wire is
not necessary for installation on GA700, GA800, CR700, or CH700 drives.
A1000
Drive
CN5-A
FE
<1>
MECHATROLINK-II Master
MECHATROLINK-II Cable
SI-T3
MECHATROLINK-II
Option
CN3