5-4
n082 : Number of Auto-Restart Attempts
Factory setting: 0
Range: 0 - 10
When a fault occurs during operation, the Drive can be programmed for an auto-restart operation to
automatically reset the fault. Auto-restart operation will use the number of reset attempts set in this
parameter, up to the maximum of 10. When set to " 0 ", no auto-restarts will be attempted.
Fault contact will not actuate (change state) during auto-restart attempts.
• The following faults can be automatically reset:
oC:
Overcurrent
ou:
Overvoltage (OV)
• The number of restart attempts available will be reset to the n082 setting when:
1. 10 minutes has elapsed without a fault occurring.
2. The RESET key, or external Fault Reset push button, is pressed.
3. Power is removed from the Drive.
n080
CARRIER FREQUENCY(kHz)
SLOPE
OUTPUT FREQUENCY(Hz)
MODE
SETTING
Maximum(Fc
MAX
)
Minimum(Fc
MIN
)
(=Fc)
Fo
F1
F2
1
2.5
2.5
0
NA
NA
CONSTANT
2
5.0
5.0
0
NA
NA
3
7.5
7.5
0
NA
NA
4
10.0
10.0
0
NA
NA
7
2.5
1.0
12
83.3
208.3
SYNCHRONOUS
8
2.5
1.0
24
41.6
104.1
9
2.5
1.0
36
27.7
69.4
n080 : Carrier Frequency
Factory Setting: 3
Range: 1 to 4; 7 to 9
The relationship between output frequency and carrier frequency is determined from the set value
of n080 .
(a) For constant carrier frequency, set to " 1 ", " 2 ", " 3 ", " 4 ".
(b) For synchronous mode, set n080 to " 7 ", " 8 ", or " 9 ". These setting values
establish carrier frequencies of 12f, 24f, or 36f, respectively.
Fc
MAX
CARRIER
FREQUENCY
SLOPE
Fc
MIN
0
F1
F2
OUTPUT FREQUENCY
5.5 CARRIER FREQUENCY
5.4 AUTO-RESTART
Содержание SI-T/ V7
Страница 1: ...V7 and V74X Drives Technical Manual Models MV and CIMR V7 Document Number TM V7 01...
Страница 16: ...xiv Intentionally Left Blank...
Страница 18: ...xvi...
Страница 22: ...1 4 Continued 1 3 PHYSICAL INSTALLATION Figure 1 1b Component Identification...
Страница 31: ...1 13 Continued 1 4 ELECTRICAL INSTALLATION Figure 1 4 Installation of Line Filter and V7 Drive...
Страница 36: ...1 18...
Страница 48: ...3 2...
Страница 52: ...4 4...
Страница 97: ...5 45 PID Block Diagram 5 28 PID CONTROL Continued...
Страница 120: ...6 10...
Страница 128: ...A1 8...
Страница 132: ...A3 2...
Страница 144: ...A6 6...
Страница 148: ...A7 4...
Страница 152: ...A8 4...
Страница 156: ...I 4...