A1-1
The Drive control circuits use various parameters to select functions and characteristics of the
Drive. Changing of parameter settings must be done in the Program mode, or by use of the
Function LEDs, if available (see Section 4).
The following table lists all parameters in numerical order. For each parameter, reference
paragraph(s) in Section 5 are listed (if applicable) where the features of the Drive affected by that
parameter are described.
Appendix 1. PARAMETER LISTING
PARA-
SETTING RANGE
SETTING
FACTORY
USER
PARA.
METER
NAME
(AND UNITS)
INCREMENT
SETTING
SETTING
REF.
0:
n001 can be read and set;
n002 - n179 read only
1:
n001 - n039 can be read and set
2:
n001 - n079 can be read and set
3:
n001 - n119 can be read and set
n001
Parameter Selection /
4:
n001 - n179 can be read and set
Initialization
5:
n001 - n179 can be read and set
1
1
5.21
Run command accepted during Program mode
6:
Clear Fault History Only
7:
Not Used
8:
2-wire Initialization (Japan Spec.)
9:
3-wire Initialization (Japan Spec.)
10: 2 wire initialization (USA Spec)
11: 3 wire initialization (USA Spec.)
n002
Control Method Selection
0:
V/f Control
1
0
2.2
1:
Open Loop Vector
0:
Digital Operator
n003
Operation Method Selection
1:
Terminal
1
1
5.13
2:
Serial Communication (Modbus)
3:
Option Card
0:
Digital Operator Pot
1:
Digital Operator
2:
Voltage Reference (0 to 10V)
3:
Current Reference (4 to 20 mA)
n004
Reference Selection
4:
Current Reference (0 to 20 mA)
5.11,
5:
Pulse Train Reference
1
2
5.13
6:
Serial Communications (Modbus)
7:
Multi-Function Analog Input (0 to 10V)
8:
Multi-Function Analog Input (4 to 20 mA)
9:
Option Card
n005
Stop Method
0:
Ramp to stop
1
0
5.24
1:
Coast to stop
n006
Reverse Prohibit
0:
Reverse Run enabled
1
0
1:
Reverse Run disabled
0:
STOP key is effective regardless of
programming of n003
n007
STOP Key Function
1:
STOP key is effective only when sequence
1
0
5.13
command (per n003) is from Digital Operator
0:
Frequency Reference from digital
n008
Reference Selection -
operator pot
1
0
5.13
Digital Operator
1:
Frequency Reference from n024
0:
ENTER key must be pressed to write-in
n009
Frequency Reference Setting
new value
1
0
5.13
Method From Digital Operator
1:
ENTER key does not have to be pressed
to write-in new value
Operation Selection
0:
Disabled (operation continues)
n010
When Digital Operator is
1:
Enabled (motor coasts to a stop and fault
1
0
5.15
Disconnected
is displayed)
n011
Frequency - Max.
50.0 to 400.0
0.1 (Hz)
60.0
n012
Voltage - Max.
0.1 to 255.0 (230V drive)
0.1 (V)
230.0
0.2 to 510.0 (460V drive)
460.0
n013
Frequency - Max.
0.2 to 400.0
0.1 (Hz)
60.0
Voltage Point
n014
Frequency - Midpoint
0.1 to 399.9
0.1 (Hz)
(Note 2)
5.27
n015
Voltage - Midpoint
0.1 to 255.0 (230V drive)
0.1 (V)
(Note 2)
0.2 to 510.0 (460V drive)
n016
Frequency - Min.
0.1 to 10.0
0.1 (Hz)
(Note 2)
n017
Voltage - Min.
0.1 to 50.0 (230V drive)
0.1 (V)
(Note 2)
0.2 to 100.0 (460V drive)
Table A1-1. V7 Parameters
Содержание SI-T/ V7
Страница 1: ...V7 and V74X Drives Technical Manual Models MV and CIMR V7 Document Number TM V7 01...
Страница 16: ...xiv Intentionally Left Blank...
Страница 18: ...xvi...
Страница 22: ...1 4 Continued 1 3 PHYSICAL INSTALLATION Figure 1 1b Component Identification...
Страница 31: ...1 13 Continued 1 4 ELECTRICAL INSTALLATION Figure 1 4 Installation of Line Filter and V7 Drive...
Страница 36: ...1 18...
Страница 48: ...3 2...
Страница 52: ...4 4...
Страница 97: ...5 45 PID Block Diagram 5 28 PID CONTROL Continued...
Страница 120: ...6 10...
Страница 128: ...A1 8...
Страница 132: ...A3 2...
Страница 144: ...A6 6...
Страница 148: ...A7 4...
Страница 152: ...A8 4...
Страница 156: ...I 4...