2-2
DIGITAL OPERATOR
DESCRIPTION
KEY SEQUENCE
DISPLAY
NOTE: 2-wire or 3-wire sequence selection must be made prior to using this startup procedure or
making any other adjustments (parameter n001).
2.2 OPEN LOOP VECTOR STARTUP
Table 2-1. Open Loop Vector Startup Procedure
Set the highest parameter
access level.
This will allow all parameters
to be viewed and set.
Press the
key until the LED
is lit on the digital operator.
DSPL
Set drive for Open Loop
Vector control.
This is accomplished by set-
ting n002 = 1
Press then .
DATA
ENTER
V
Set motor rated voltage.
(This can be obtained from
the nameplate of the motor.)
Press and hold
until n012 is dis-
played on the digital operator.
V
PRGM
Then press
.
DATA
ENTER
Use the
&
keys until the
number in the display matches the motor
rated voltage.
V
V
Then press
.
DATA
ENTER
PRGM
PRGM
PRGM
PRGM
PRGM
PRGM
PRGM
PRGM
PRGM
PRGM
PRGM
Use the
&
keys to set a “1”
in the display.
V
V
Then press
.
DATA
ENTER
Press .
DATA
ENTER
Press three
times.
V
Press .
DATA
ENTER
(1)
(1)
Содержание SI-T/ V7
Страница 1: ...V7 and V74X Drives Technical Manual Models MV and CIMR V7 Document Number TM V7 01...
Страница 16: ...xiv Intentionally Left Blank...
Страница 18: ...xvi...
Страница 22: ...1 4 Continued 1 3 PHYSICAL INSTALLATION Figure 1 1b Component Identification...
Страница 31: ...1 13 Continued 1 4 ELECTRICAL INSTALLATION Figure 1 4 Installation of Line Filter and V7 Drive...
Страница 36: ...1 18...
Страница 48: ...3 2...
Страница 52: ...4 4...
Страница 97: ...5 45 PID Block Diagram 5 28 PID CONTROL Continued...
Страница 120: ...6 10...
Страница 128: ...A1 8...
Страница 132: ...A3 2...
Страница 144: ...A6 6...
Страница 148: ...A7 4...
Страница 152: ...A8 4...
Страница 156: ...I 4...