YASKAWA
SIEP C730600 0E YAI Modbus TCP/IP Technical Manual
53
Table 10.2 Option Compatibility
Option
Connector
Number of Options Possible
PG-B3, PG-X3
CN5-B, C
2
PG-RT3
, PG-F3
CN5-C
1
DO-A3, AO-A3
CN5-A, B, and C
1
SI-C3, SI-N3, SI-P3, SI-S3, SI-T3, SI-ET3,
SI-ES3, SI-B3, SI-M3,
SI-W3
, SI-EM3
, SI-EM3D
, SI-EN3
, SI-EN3D
, SI-
EP3,
AI-A3
, DI-A3
CN5-A
1
*1
To connect two PG options, use the CN5-C and CN5-B connectors. To connect only one PG option, use the CN5-C connector.
*2
If you use the motor switching function, you cannot use this option.
*3
Not available with 1000-Series drive models with a capacities between 450 and 630 kW.
*4
To use AI-A3 and DI-A3 input statuses as monitors, connect the options to one of CN5-A, CN5-B, or CN5-C.
11
Option Installation
Verify the following installation conditions to make sure that other devices and machinery used with this option
and drive also comply with EMC guidelines:
1.
Use dedicated shield cable for the option and external device (encoder, I/O device, master), or run the
wiring through a metal conduit.
2.
Keep wiring as short as possible and ground the largest possible surface area of the shield to the metal
panel according to
and
.
Figure 11.1 Option Installation for CE Compliance: 1000-Series, GA700, GA800
Figure 11.2 Option Installation for CE Compliance: GA500, HV600
3.
Ground the largest possible surface area of the shield to the metal panel.
Use cable clamps if possible.