PVI 36TL Installation and Operation Manual (Rev H)
DOCR-070588-H
Page
84
of
120
GridVmaxRecT(V)
Recovery threshold value of
Max. grid voltage
{200.0, 518.0, 533.0}
GridVminRecT(V)
Recovery threshold value of
Min. grid voltage
{0, 432.4, 480.0}
GridVRecT(S)
Recovery time of grid voltage
protection
{0, 300.00, 600.00}
GridF.Max1(Hz)
Protection threshold value of
Level 1 Max. grid frequency
{50.00, 60.50, 66.00}
FmaxTripT1(S)
Trip time of Level 1 Max. grid
frequency
{0, 0.16, 600.00}
GridF.Min1(Hz)
Protection threshold value of
Level 1 Min. grid frequency
{45.00, 59.30, 60.00}
FminTripT1(S)
Trip time of Level 1 Min. grid
frequency
{0, 0.16, 600.00}
GridF.Max2(Hz)
Protection threshold value of
Level 2 Max. grid frequency
{50.00, 61.00, 66.00}
FmaxTripT2(S
)
Trip time of Level 2 Max. grid
frequency
{0, 0.05, 600.00}
GridF.Min2(Hz)
Protection threshold value of
Level 2 Min. grid frequency
{45.00, 57.00, 60.00}
FminTripT2(S)
Trip time of Level 2 Min. grid
frequency
{0, 0.16, 600.00}
GridFmaxRecT(Hz)
Recovery threshold value of
Max. grid frequency
{49.00, 60.40, 66.00}
GridFminRecT(Hz)
Recovery threshold value of
Min. grid frequency
{45.00, 59.40, 60.00}
GridFRecT(S)
Recovery time of grid
frequency protection
{0, 300.00, 600.00}
GridV.Unbal(%)
Threshold value of grid
voltage unbalance
{0.1, 2.6, 10.0}
(2) ”3 ON/OFF” menu: Set up the start-up and shut-down control parameters.
Table 4.4 - Start-Up and Turn-Off Control Parameters
Parameter name
Description
Setup range (lower limit,
default & upper limit)
PVStartVol(V)
PV start-up voltage
{300.0, 330.0, 400.0}
SoftStep(KW/S)
Soft step
{0.01,1.44,2.88}