PVI 36TL Installation and Operation Manual (Rev H)
DOCR-070588-H
Page
88
of
120
QuCurveQ2(%)
(-100.0%, -50.0%, 100.0%)
See Figure 5-18
QuCurveU1i(V)
(422.4, 441.6, 480.0)
See Figure 5-18
QuCurveQ1i(%)
(-100.0%, 0.0%, 100.0%)
See Figure 5-18
QuCurveU2i(V)
(422.4, 432.0, 480.0)
See Figure 5-18
QuCurveQ2i(%)
(-100.0%, 50.0%, 100.0%)
See Figure 5-18
QuCurvTripP(%)
(5.0%, 20.0%, 100.0%)
Qu curve trip power
QuCurveReP(%)
(5.0%, 5.0%, 100.0%)
Qu curve revocation
power
3. “FreqDeratCtrl” menu: Set up the parameters of over-frequency active power
deraring.
(4) ”6 OtherProtect” menu: set up the threshold value of leakage current and output
DC component protection:
Table 4.6 - Protection Parameters of Leakage Current and Output DC Component
Parameter name
Description
Setup range (lower limit, default &
upper limit)
LeakCurMax(mA)
Leakage current
Max. limit
{300, 300, 500}*
IdcMax(mA)
DC component
current Max. limit
{216, 216, 500}*
* UL 1741 ground fault requirements
INSTRUCTION:
The “FreqDeratCtrl” function is not available for the IEEE-1547 grid
standard.