Start Up 4 - 9
"
21. Check the signal for proper polarity. Observe if the speed command can achieve the minimum and maximum speeds
desired. If not, perform the following:
For 0-10Vdc input (Terminal A1)
1.
With no input, adjust Bias (H3-03 setting) until an output of “0.0 Hz” is obtained.
2.
With full-scale input, adjust Gain (H3-02 setting) until an output of “60.0 Hz” (or other desired maximum
frequency) is obtained.
For 4-20mA input (Terminal A2)
1.
With 4mA input, adjust Bias (H3-11 setting) until an output of “0.0 Hz” is obtained.
2. With 20 mA input, adjust Gain (H3-10 setting) until an output of “60.0 Hz”
(or other desired maximum frequency) is obtained.
THIS COMPLETES THE DRIVE START UP PROCEDURE.
Содержание P7
Страница 1: ...P7 Drive User Manual Model P7U Document Number TM P7 01...
Страница 58: ...Electrical Installation 2 30...
Страница 74: ...Digital Operator 3 16...
Страница 84: ...Start Up 4 10 Notes...
Страница 144: ...Programming 5 60 Notes...
Страница 210: ...Capacity Related Parameters B 6 Notes...
Страница 238: ...Spare Parts F 4 Notes...
Страница 239: ...EMC Compatibility G 1 Appendix G EMC Compatibility EMC Compatibility G 2 Electromagnetic Compatibility EMC G 3...
Страница 244: ...EMC Compatibility G 6 Notes...