Physical Installation 1 - 14
Installation Orientation and Clearances
Install the Drive vertically so as not to reduce the cooling efficiency. When installing the Drive, always provide the following
installation clearances to allow normal heat dissipation. Ensure that the heatsink is against a closed surface to avoid diverting
cooling air around the heatsink.
Fig 1.8 Drive Installation Orientation and Clearance
IMPORTANT
1. The same clearance is required horizontally and vertically for both Open Chassis (IP00) and NEMA
Type 1 Drives.
2. Always remove the top and bottom protection covers before installing a CIMR-P7U2018/4018 and
smaller Drive in a panel.
Always provide enough clearance for lifting eye bolts and the main circuit wiring when installing a
CIMR-P7U2022/4030 and larger Drive in a panel.
4.75 in (120 mm. minimum)
4.75 in (120 mm. minimum)
Air
Air
Vertical Clearance
Horizontal Clearance
1.2 in
(30.5 MM.) min.
1.2 in
(30.5 mm. minimum)
1.2 in
(30.5 mm. minimum)
4.75 in (50 mm. minimum)
4.75 in (120 mm. minimum)
Содержание P7
Страница 1: ...P7 Drive User Manual Model P7U Document Number TM P7 01...
Страница 58: ...Electrical Installation 2 30...
Страница 74: ...Digital Operator 3 16...
Страница 84: ...Start Up 4 10 Notes...
Страница 144: ...Programming 5 60 Notes...
Страница 210: ...Capacity Related Parameters B 6 Notes...
Страница 238: ...Spare Parts F 4 Notes...
Страница 239: ...EMC Compatibility G 1 Appendix G EMC Compatibility EMC Compatibility G 2 Electromagnetic Compatibility EMC G 3...