u
Three-Phase 400 V Class Drive Models 4A0002 to 4A0031
Table A.4 Power Ratings (Three-Phase 400 V Class)
Item
Specification
Drive Models
4A0002 4A0004 4A0005 4A0007 4A0009 4A0011 4A0018 4A0023 4A0031
Maximum Applicable
Motor Capacity (HP)
ND Rating
0.75
2
3
3
5
7.5
10
15
20
Input
Input Current (A)
ND Rating
2.1
4.3
5.9
8.1
9.4
14
20
24
38
Rated Voltage
Rated Frequency
Three-phase: 380 to 480 Vac 50/60 Hz/510 to 680 Vdc
Allowable Voltage Fluctuation
-15 to 10%
Allowable Frequency Fluctuation
±5%
Input Power (kVA)
ND Rating
2.3
4.3
6.1
8.1
10.0
14.5
19.4
28.4
37.5
Output
Rated Output
Capacity (kVA)
ND Rating
1.6
3.1
4.1
5.3
6.7
8.5
13.3
17.5
24
Rated Output
Current (A)
ND Rating
2.1
4.1
5.4
6.9
8.8
11.1
17.5
23
31
Overload Tolerance
ND Rating: 120% of rated output current for 60 s
(Derating may be required for applications that start and stop frequently)
Carrier Frequency
User-adjustable between 1 and 15 kHz
Maximum Output Voltage (V)
Three-phase: 380 to 480 V (proportional to input voltage)
Maximum Output Frequency (Hz)
400 Hz (user-adjustable)
<3> DC is not available for UL/CE standards.
<4> Rated motor capacity is calculated with a rated output voltage of 440 V.
<5> Carrier frequency default setting is Swing PWM 1 (C6-02 = 7). C6-02 settings 1, 7, 8, 9, and A do not require current derating. All other settings
raise the carrier frequency and require current derating.
A.1 Power Ratings
YASKAWA ELECTRIC TOEP YAIP1U 01B YASKAWA AC Drive - P1000 Quick Start Guide
173
A
Specifications
Содержание P1000
Страница 255: ......