H2 Multi-Function Digital Output Settings
H2-
oo
Setting
Function
Description
Page
1E
Restart enabled
Closed: An automatic restart is performed
–
1F
Motor overload alarm (oL1)
Closed: oL1 is at 90% of its trip point or greater. An oH3 situation also triggers this alarm.
–
20
Drive overheat pre-alarm (oH) Closed: Heatsink temperature exceeds the parameter L8-02 value.
–
22
Mechanical weakening
detection
Closed: Mechanical weakening detected.
–
2F
Maintenance period
Closed: Cooling fan, electrolytic capacitors, IGBTs, or the soft charge bypass relay may require
maintenance.
–
37
During frequency output
Open: Either the drive has stopped or baseblock, DC Injection Braking, or Initial Excitation is
being performed.
Closed: Drive is running the motor (not in a baseblock state and DC Injection is not being
performed).
–
38
Drive enabled
Closed: Multi-function input set for “Drive enable” is closed (H1-
oo
= 6A)
–
39
Watt hour pulse output
Output units are determined by H2-06. Outputs a pulse every 200 ms to indicate the kWh count.
–
3C
LOCAL/REMOTE status
Open: REMOTE
Closed: LOCAL
–
3D
During speed search
Closed: Speed Search is being executed.
–
3E
PID feedback low
Closed: PID feedback level is too low.
–
3F
PID feedback high
Closed: The PID feedback level is too high.
–
4A
During KEB Ride-Thru
Closed: KEB Ride-Thru is being performed.
–
4C
During fast stop
Closed: A Fast Stop command has been entered from the operator or input terminals.
–
4D
oH Pre-alarm time limit
Closed: oH pre-alarm time limit has passed.
–
4E
Braking transistor fault (rr)
Closed: The built-in dynamic braking transistor failed.
–
4F
Braking resistor overheat (oH) Closed: The dynamic braking resistor has overheated.
–
50
Waiting to Run
Closed: b1-11 Timer is active.
–
51
Sequence timer 1
Closed: Sequence timer 1 is active.
–
52
Sequence timer 2
Closed: Sequence timer 2 is active.
–
53
Sequence timer 3
Closed: Sequence timer 3 is active.
–
54
Sequence timer 4
Closed: Sequence timer 4 is active.
–
58
Underload detection
Closed: Underload is detected.
–
60
Internal cooling fan alarm
Closed: Internal cooling fan alarm
–
71
Secondary PI Feedback Low
Closed: PI2 feedback level is too low.
–
72
Secondary PI Feedback High Closed: The PI2 feedback level is too high.
–
100 to 192 Function 0 to 92 with inverse
output
Inverts the output switching of the multi-function output functions.
Set the last two digits of 1
oo
to reverse the output signal of that specific function.
–
u
H3: Multi-Function Analog Inputs
No.
(Addr.
Hex)
Name
Description
Values
Page
H3-01
(410)
Terminal A1 Signal Level
Selection
0: 0 to 10 V
1: -10 to 10 V
2: 4 to 20 mA
3: 0 to 20 mA
Note:
Use Jumper S1 to set input terminal A1 for a current or voltage
input signal.
Default: 0
Range: 0 to 3
H3-02
(434)
Terminal A1 Function
Selection
Sets the function of terminal A1.
Default: 0
Range: 0 to 26
H3-03
(411)
Terminal A1 Gain Setting
Sets the level of the input value selected in H3-02 when 10 V is input at
terminal A1.
Default: 100.0%
Min.: -999.9
Max.: 999.9
H3-04
(412)
Terminal A1 Bias Setting
Sets the level of the input value selected in H3-02 when 0 V is input at terminal
A1.
Default: 0.0%
Min.: -999.9
Max.: 999.9
B.6 H Parameters: Multi-Function Terminals
206