6 CANopen-Lift Option Related Drive Parameters
14
YASKAWA ELECTRIC
SIEP YEUOCL1 01A CANopen-Lift Communication Option Installation Manual
b1-01 to 6,
b1-02 to 6,
H5-13 to 5.
11.
Powercycle the inverter drive.
◆
EDS File
For easy network implementation of drives equipped with a Communication Option card, the EDS file (version
ESI_SIS3L_OPT_V_2_01_04
or later) can be obtained from these sources:
•
Europe:
http://www.yaskawa.eu.com
•
Japan:
http://www.e-mechatronics.com
•
USA:
http://www.yaskawa.com
•
Other areas: contact a YASKAWA representative
6
CANopen-Lift Option Related Drive Parameters
Some drive parameters have influence on some functions of the communication option card. Check these
parameters before starting network communications.
Table 6.1 Parameter Settings
No.
Name
Description
Default
b1-01
Frequency Reference Selection Selects the frequency reference input source
0: Operator - Digital preset speed d1-01 to d1-17
1: Terminals - Analog input terminals
2: MEMOBUS/Modbus communications
3: Option card
4: Pulse Input (Terminal RP)
6: DCP/CANopen-Lift
1
b1-02
Run Command Selection
Selects the run command input source
0: Digital Operator - RUN and STOP keys
1: Digital input terminals Sx
2: MEMOBUS/Modbus communications
3: Option card
6: DCP/CANopen-Lift
1
F6-01
Operation Selection after
Communications Error
Determines drive response when a bUS error is detected during
communications
0: Ramp to Stop
1: Coast to Stop
2: Fast-Stop
3: Alarm Only
*1
1
F6-02
External Fault Detection
Conditions (EF0)
Sets the condition for external fault detection (EF0)
0: Always detected
1: Detected only during operation
0
F6-03
Stopping Method for External
Fault from Communication
Option Board
Determines drive response for external fault input (EF0) detection
0: Ramp to Stop
1: Coast to Stop
2: Fast-Stop
3: Alarm Only
1