YASKAWA
TOEPC710616134G AC Drive L1000A Technical Manual Addendum
39
Figure 6.6 Inspection Travel with V0 and Stopping with Stop Command
Re-leveling Travel not Dependent on Remaining Distance :
The re-leveling travel not depending on remaining distance is used for DCP3 and in special cases for DCP4. With
DCP4, re-leveling travel dependent on remaining distance is also applied.
Re-leveling Travel not Dependent on Remaining Distance without Electric Stop :
Many lift controllers treat re-leveling as a special case. The mechanical brake and the motor contactors are also
switched off along with the re-leveling speed (see step (3)).
1. Before the travel starts, the speed mode "Releveling [bit G1]" (VN) is transmitted.
2. The travel starts with activation of travel command bit B1, but the stop switch is not set.
3. Travel command bit B1 and drive controller enable bit B0 are switched off at the same time.
EN
Содержание L1000A CIMR-LC F Series
Страница 1: ...AC Drive L1000A For Lift Applications Technical Manual Addendum Type CIMR LCxFxxxxxxx 913x Web...
Страница 2: ...This Page Intentionally Blank 2 YASKAWA TOEPC710616134G AC Drive L1000A Technical Manual Addendum...
Страница 97: ...15 Appendix YASKAWA TOEPC710616134G AC Drive L1000A Technical Manual Addendum 97 15 Appendix EN...
Страница 98: ...15 Appendix 98 YASKAWA TOEPC710616134G AC Drive L1000A Technical Manual Addendum...
Страница 99: ...15 Appendix YASKAWA TOEPC710616134G AC Drive L1000A Technical Manual Addendum 99 EN...
Страница 100: ...15 Appendix 100 YASKAWA TOEPC710616134G AC Drive L1000A Technical Manual Addendum...
Страница 101: ...15 Appendix YASKAWA TOEPC710616134G AC Drive L1000A Technical Manual Addendum 101 EN...
Страница 102: ...15 Appendix 102 YASKAWA TOEPC710616134G AC Drive L1000A Technical Manual Addendum...