Object ID
Object Name
(Network Display, if Different)
Modbus Register (Hex.)
Active Text
Inactive Text
PV Access
(Drv Startup Complete)
BV40
Low Voltage Detect
002C: Bit 7
ON
OFF
R
BV41
Base Block
002C: Bit 8
ON
OFF
R
BV42
Frequency Reference Mode
(Frequency Ref Mode)
002C: Bit 9
LOCAL
COM
R
BV43
Run Command Mode
002C: Bit A
LOCAL
COM
R
BV44
Over Torque Detect
002C: Bit B
ON
OFF
R
BV45
Frequency Reference Loss
(Frequency Ref Loss)
002C: Bit C
ON
OFF
R
BV46
Retry Error
002C: Bit D
ON
OFF
R
BV55
Parameter Accept
Executes the RAM enter
command.
ON
OFF
W
BV56
Parameter Enter
Executes the ROM enter
command.
ON
OFF
W
BV58
Bypass Forward Run Cmd
(BYP Run Fwd CMD)
0001: Bit 0
ON
OFF
C
BV59
Bypass Reverse Run Cmd
(BYP Run Rev CMD)
0001: Bit 1
ON
OFF
C
BV60
Emergency Override Drive Reverse
(Em Over DRV REV CMD)
Internal
ON
OFF
C
BV61
Bypass Transfer to Bypass Cmd
(BYP Xfer to BYP CMD)
8400: Bit 3
ON
OFF
C
BV62
Emergency Overide Bypass
(Em Over BYPASS CMD)
8400: Bit 4
ON
OFF
C
BV63
Emergency Override Drive Forward
(Em Over DRV FWD CMD)
Internal
ON
OFF
C
BV64
Bypass Motor OR Select Command
(BYP Mtr OR Sel CMD)
8400: Bit 6
ON
OFF
C
BV65
Bypass Motor AND Select Command
(BYP Mtr AND Sel CMD)
8400: Bit 7
ON
OFF
C
Bypass BYPASS Select Command
(BYP BYPASS Sel CMD)
8400: Bit C
BYP
DRV
C
BV70
Bypass Fault Reset Command
(BYP Fault Reset CMD)
8400: Bit D
ON
OFF
C
BV71
Bypass External Fault Command
(BYP Ext Fault CMD)
8400: Bit E
ON
OFF
C
BV72
Bypass DI-01 Command
(BYP DI-01 Command)
8402: Bit 0
ON
OFF
C
BV73
Bypass DI-02 Command
(BYP DI-02 Command)
8402: Bit 1
ON
OFF
C
BV74
Bypass DI-03 Command
(BYP DI-03 Command)
8402: Bit 2
ON
OFF
C
BV75
Bypass DI-04 Command
(BYP DI-04 Command)
8402: Bit 3
ON
OFF
C
BV76
Bypass DI-05 Command
(BYP DI-05 Command)
8402: Bit 4
ON
OFF
C
BV77
Bypass DI-06 Command
(BYP DI-06 Command)
8402: Bit 5
ON
OFF
C
BV78
Bypass DI-07 Command
(BYP DI-07 Command)
8402: Bit 6
ON
OFF
C
BV79
Bypass DI-08 Command
(BYP DI-08 Command)
8402: Bit 7
ON
OFF
C
BV80
Bypass HAND Mode Status
(BYP HAND Mode Status)
8784: Bit 0
ON
OFF
R
BV81
Bypass OFF Mode Status
(BYP OFF Mode Status)
8784: Bit 1
ON
OFF
R
BV82
Bypass AUTO Mode Status
8784: Bit 2
ON
OFF
R