![YASKAWA JOHB-SMP3 Скачать руководство пользователя страница 25](http://html1.mh-extra.com/html/yaskawa/johb-smp3/johb-smp3_technical-manual_3511125025.webp)
YASKAWA
SIEP C730600 0MA BACnet/IP Technical Manual
25
Object ID
Object Name
(Network Display, if Different)
Modbus Register (Hex.)
Range
Unit
PV Access
(Drv Anlg In 3 Level)
AI4
Bypass Analog Input 1 Level
(Byp Anlg In 1 Level)
8795
0 - 100.0
%
R
AI6
Display Format o1-03
0502
0 - 65535
-
R
AI7
Scale Format b5-20
01E2
0 - 65535
-
R
AI8
Inverter Model o2-04
0508
0 - 65535
-
R
AI9
Rated Current n9-01
05D0
0 - 6553.5 (for drives
rated higher than 11
kVA)
0 - 655.35 (for drives
rated 11 kVA or lower)
A
R
AI10
Motor Current UB-01
8780
0 - 655.35
A
R
AI11
Contactor Voltage
8790
0 - 65535
V
R
*1
Not available on all drives. Refer to the Technical Manual of your drive, and check if the Modbus register of the applicable object
exists.
*2
Available on bypasses only.
◆
Analog Output Objects
Object ID
Object Name
(Network Display, if Different)
Modbus Register (Hex.)
Range
Unit
PV Access
AO1
Drive Analog Output 1 Level
Drive Terminal FM
(set H4-01 = 0)
(Drv Anlg Out1 Level)
0007
0 - 100.0
%
C
AO2
Drive Analog Output 2 Level
Drive Terminal AM
(set H4-01 = 0)
(Drv Anlg Out2 Level)
0008
0 - 100.0
%
C
*1
Not available on all drives. Refer to the Technical Manual of your drive, and check if the Modbus register of the applicable object
exists.
◆
Analog Value Objects
Object ID
Object Name
(Network Display, if Different)
Modbus Register (Hex.)
Range
Unit
PV Access
AV1
Drive Operation Command
(Operation Cmd)
0001
0 - 65535
Bitmap
C
AV2
Frequency Cmd
0002
0 - 600.00
Determined by o1-03
C
AV3
PI Setpoint Cmd
0006
0 - 100.00
%
C
AV4
Drive Multi-Function Output Command
(MF Output Cmd)
•
Bit 0: Multi-FunctionDigital Output 1
(terminal M1-M2)
•
Bit 1: Multi-FunctionDigital Output 2
(terminal M3-M4)
•
Bit 2: Multi-Function Digital Output 3
(terminal M5-M6)
(Z1000U: MD-ME-MF)
•
Bit 3: Reserved
•
Bit 4: Reserved
•
Bit 5: Reserved
•
Bit 6: Enables the function in bit 7
•
Bit 7: Fault Contact Output (terminal
MA-MB-MC)
•
Bit 8 to F: Reserved
Note:
When using AV4, do not use BO1 to
BO3 or BV12.
0009
0 - 255
Bitmap
C
AV5
Drive Reference Select Command
(Reference Select Cmd)
•
Bit 0: Reserved
•
Bit 1: PID Setpoint Input
000F
0 - 32767
Bitmap
C