SIEP C730600 0MA BACnet/IP Technical Manual
19
No.
(Hex.)
Name
Description
Default
(Range)
Note:
When you set
F6-08
to
1
and you then use
A1-03
to initialize the drive, the drive will not
change this setting value.
F6-14
(03BB)
Bus Error Auto Reset
Sets the automatic reset function for
bUS [Option Communication Error]
.
0 : Disabled
1 : Enabled
Note:
Changes to this parameter take effect immediately. It is not necessary to cycle power on the
drive.
0
(0, 1)
F6-15
(0B5B)
Comm. Option Parameters
Reload
Sets when the drive will activate the
F6-xx/F7-xx
communications-related parameters that you
changed. Use this parameter as an alternative to cycling power to the drive to active parameters.
0 : Reload at Next Power Cycle
1 : Reload Now
2 : Cancel Reload Request
Note:
•
F6-15
is reset to
0
after setting
1
or
2
.
•
This parameter is not available in Z1000U drive.
•
Changes to this parameter take effect immediately. It is not necessary to cycle power on the
drive.
0
(0 - 2)
F6-16
(0B8A)
Gateway Mode
Sets the gateway mode operation and the number of connected slave drives..
0 : Disabled
1 : Enabled: 1 Slave Drive
2 : Enabled: 2 Slave Drives
3 : Enabled: 3 Slave Drives
4 : Enabled: 4 Slave Drives
Note:
This parameter is not available in Z1000U drive.
0
(0 - 4)
F6-48
(02FE)
BACnet Device Object
Identifier 0
Sets the Instance Identifier of the BACnet Device Object, where the
F6-48
value is the least
significant word.
Note:
This parameter and
F6-49
set the Instance Identifier of the BACnet Device Object.
Example 1: Set the Device Object Instance Identifier to
1234
. 1234 decimal is equal to 4D2
(Hex.). Set
F6-48 = 4D2 (Hex.)
and
F6-49 = 0 (Hex.)
.
Example 2: Set the Device Object Instance Identifier to
1234567
. 1234567 decimal is equal to
12D687 (Hex.). Set
F6-48 = D687 (Hex.)
and
F6-49 = 12 (Hex.)
.
1
(0 - FFFF (Hex.))
F6-49
(02FF)
BACnet Device Object
Identifier 1
Sets the Instance Identifier of the BACnet Device Object, where the
F6-49
value is the most
significant word.
Note:
This parameter and
F6-48
set the Instance Identifier of the BACnet Device Object.
Example 1: Set the Device Object Instance Identifier to
1234
. 1234 decimal is equal to 4D2
(Hex.). Set
F6-48 = 4D2 (Hex.)
and
F6-49 = 0 (Hex.)
.
Example 2: Set the Device Object Instance Identifier to
1234567
. 1234567 decimal is equal to
12D687 (Hex.). Set
F6-48 = D687 (Hex.)
and
F6-49 = 12 (Hex.)
.
0
(0 - 3F (Hex.))
F7-01
(03E5)
IP Address 1
Sets the static/fixed IP address. Sets the most significant octet.
Note:
•
This parameter is only effective when
F7-13 = 0 [Address Mode at Startup = Static]
.
•
All IP Addresses must be unique.
•
You must cycle power to the drive for the changes to take effect. For non-Z1000U drives,
setting
F6-15 = 1 [Comm. Option Parameters Reload = Reload Now]
enables
communication OPT parameter changes without turning on the power again.
192
(0 - 255)
F7-02
(03E6)
IP Address 2
Sets the static/fixed IP address. Sets the second most significant octet.
Note:
•
This parameter is only effective when
F7-13 = 0 [Address Mode at Startup = Static]
.
•
All IP Addresses must be unique.
•
You must cycle power to the drive for the changes to take effect. For non-Z1000U drives,
setting
F6-15 = 1 [Comm. Option Parameters Reload = Reload Now]
enables
communication OPT parameter changes without turning on the power again.
168
(0 - 255)
F7-03
(03E7)
IP Address 3
Sets the static/fixed IP address. Sets the third most significant octet.
Note:
•
This parameter is only effective when
F7-13 = 0 [Address Mode at Startup = Static]
.
•
All IP Addresses must be unique.
•
You must cycle power to the drive for the changes to take effect. For non-Z1000U drives,
setting
F6-15 = 1 [Comm. Option Parameters Reload = Reload Now]
enables
communication OPT parameter changes without turning on the power again.
1
(0 - 255)
F7-04
(03E8)
IP Address 4
Sets the static/fixed IP address. Sets the fourth most significant octet.
Note:
•
This parameter is only effective when
F7-13 = 0 [Address Mode at Startup = Static]
.
•
All IP Addresses must be unique.
•
You must cycle power to the drive for the changes to take effect. For non-Z1000U drives,
setting
F6-15 = 1 [Comm. Option Parameters Reload = Reload Now]
enables
communication OPT parameter changes without turning on the power again.
20
(0 - 255)
F7-05
(03E9)
Subnet Mask 1
Sets the static/fixed Subnet Mask. Sets the most significant octet.
255
(0 - 255)