324
YASKAWA
TOEPYAIHV6002A HV600 Drive Programming
■
100 to 1C4: Inverse Outputs of 0 to C4
Setting Value
Function
Description
100 to 1C4
Inverse Outputs of 0 to C4
Causes inverse output of the function for the selected MFDO. Uses the last two digits of 1xx to select which function to inversely
output.
For example, set
H2-xx = 10E
for the inverse output of
E [Fault]
.
◆
H3: Analog Inputs
WARNING!
Sudden Movement Hazard. Do test runs and examine the drive to make sure that the command references are correct.
If you set the command reference incorrectly, it can cause damage to the drive or serious injury or death.
Drives have two analog input terminals, terminals A1 and A2.
H3 parameters
select the functions set to these analog
input terminals and adjust signal levels.
shows the functions that you can set to analog input terminals. Use
H3-02 and H3-10 [MFAI Function
Selection]
to set functions.
Table 2.55 MFAI Setting Values
Setting
Value
Function
Ref.
0
Frequency Reference
1
Frequency Gain
2
Auxiliary Frequency Reference 1
3
Auxiliary Frequency Reference 2
4
Output Voltage Bias
5
Accel/Decel Time Gain
6
DC Injection Braking Current
7
Torque Detection Level
8
Stall Prevent Level During Run
9
Output Frequency Lower Limit
B
PID Feedback
C
PID Setpoint
D
Frequency Bias
E
Motor Temperature (PTC Input)
F
Not Used
10
Forward Torque Limit
Setting
Value
Function
Ref.
11
Reverse Torque Limit
12
Regenerative Torque Limit
15
General Torque Limit
16
Differential PID Feedback
1F
Not Used
24
PID Feedback Backup
25
PI2 Control Setpoint
26
PI2 Control Feedback
27
PI Auxiliary Control Feedback
2B
Emergency Override PID Feedback
2C
Emergency Override PID Setpoint
2D
Differential Level Source
2E
Hand Frequency Ref or Setpoint
30
DWEZ Analog Input 1
31
DWEZ Analog Input 2
Note:
All analog input scaling uses gain and bias for adjustment. Set the gain and bias values correctly.
V/f
OLV/PM
OLV/PM
EZOLV
Содержание HV600
Страница 2: ...This Page Intentionally Blank 2 YASKAWA TOEPYAIHV6002A HV600 Drive Programming...
Страница 16: ...i 3 Warranty Information 16 YASKAWA TOEPYAIHV6002A HV600 Drive Programming...
Страница 158: ...1 22 Defaults by o2 04 Drive Model kVA Selection 158 YASKAWA TOEPYAIHV6002A HV600 Drive Programming...
Страница 506: ...2 14 Y Application Features 506 YASKAWA TOEPYAIHV6002A HV600 Drive Programming...