334
YASKAWA
TOEPYAIHV6002A HV600 Drive Programming
Figure 2.77 Torque Limits from Parameters and Analog Inputs
■
11: Reverse Torque Limit
Setting Value
Function
Description
11
Reverse Torque Limit
Enters the load torque limit if the motor rated torque is 100%.
Note:
When you use
L7-01 to L7-04
and analog inputs to set torque limits for the same quadrant, it will enable the lower torque limit.
■
12: Regenerative Torque Limit
Setting Value
Function
Description
12
Regenerative Torque Limit
Enters the regenerative torque limit if the motor rated torque is 100%.
Note:
When you use
L7-01 to L7-04
and analog inputs to set torque limits for the same quadrant, it will enable the lower torque limit.
■
15: General Torque Limit
Setting Value
Function
Description
15
General Torque Limit
Enters the torque limit that is the same for all quadrants for forward, reverse, and regenerative operation if the motor rated torque is
100%.
■
16: Differential PID Feedback
Setting Value
Function
Description
16
Differential PID Feedback
Enters the PID differential feedback value if the full scale analog signal (10 V or 20 mA) is 100%.
The drive uses the deviation between the PID feedback and the differential feedback value signals to calculate the PID
input.
■
1F: Not Used
Setting Value
Function
Description
1F
Not Used
Use this setting for unused terminals or to use terminals in through mode.
V/f
OLV/PM
OLV/PM
EZOLV
V/f
OLV/PM
OLV/PM
EZOLV
V/f
OLV/PM
OLV/PM
EZOLV
V/f
OLV/PM
OLV/PM
EZOLV
V/f
OLV/PM
OLV/PM
EZOLV
Содержание HV600
Страница 2: ...This Page Intentionally Blank 2 YASKAWA TOEPYAIHV6002A HV600 Drive Programming...
Страница 16: ...i 3 Warranty Information 16 YASKAWA TOEPYAIHV6002A HV600 Drive Programming...
Страница 158: ...1 22 Defaults by o2 04 Drive Model kVA Selection 158 YASKAWA TOEPYAIHV6002A HV600 Drive Programming...
Страница 506: ...2 14 Y Application Features 506 YASKAWA TOEPYAIHV6002A HV600 Drive Programming...