10.13 o: Keypad-Related Settings
YASKAWA
SIEPC71061723A YASKAWA AC Drive CR700 Technical Manual
527
◆
o3: Copy Keypad Function
No.
(Hex.)
Name
Description
Default
(Range)
Ref.
o3-01
(0515)
Copy Keypad Function
Selection
Sets the function to use the keypad to save and copy drive parameters to a different
drive.
0 : Copy Select
1 : Backup (drive → keypad)
2 : Restore (keypad → drive)
3 : Verify (check for mismatch)
0
(0 - 3)
o3-02
(0516)
Copy Allowed Selection
Sets the copy function when
o3-01 = 1 [Copy Keypad Function Selection = Backup
(drive → keypad)]
.
0 : Disabled
1 : Enabled
0
(0, 1)
o3-04
(0B3E)
Select Backup/Restore
Location
Sets the storage location for drive parameters when you back up and restore parameters.
This parameter is only available when using an LCD keypad.
0 : Memory Location 1
1 : Memory Location 2
2 : Memory Location 3
3 : Memory Location 4
0
(0 - 3)
o3-05
(0BDA)
Select Items to Backup/
Restore
Sets which parameters are backed up, restored, and referenced. This parameter is only
available on an LCD keypad.
0 : Standard Parameters
1 : St DWEZ Parameters
0
(0, 1)
o3-06
(0BDE)
Auto Parameter Backup
Selection
Sets the function that automatically backs up parameters. This parameter is only
available when using an LCD keypad.
0 : Disabled
1 : Enabled
1
(0, 1)
o3-07
(0BDF)
Auto Parameter Backup
Interval
Sets the interval at which the automatic parameter backup function saves parameters
from the drive to the keypad.
Note:
This parameter is only available when using an LCD keypad.
0 : Every 10 minutes
1 : Every 30 minutes
2 : Every 60 minutes
3 : Every 12 hours
1
(0 - 3)
◆
o4: Maintenance Monitors
No.
(Hex.)
Name
Description
Default
(Range)
Ref.
o4-01
(050B)
Elapsed Operating Time
Setting
Sets the initial value of the cumulative drive operation time in 10-hour units.
0 h
(0 - 9999 h)
o4-02
(050C)
Elapsed Operating Time
Selection
Sets the condition that counts the cumulative operation time.
0 : U4-01 Shows Total Power-up Time
1 : U4-01 Shows Total RUN Time
0
(0, 1)
o4-03
(050E)
Fan Operation Time
Setting
Sets the value from which to start the cumulative drive cooling fan operation time in 10-
hour units.
0 h
(0 - 9999 h)
o4-05
(051D)
Capacitor Maintenance
Setting
Sets the
U4-05 [CapacitorMaintenance]
monitor value.
0%
(0 - 150%)
o4-07
(0523)
Softcharge Relay
Maintenance Set
Sets the
U4-06 [PreChargeRelayMainte]
monitor value.
0%
(0 - 150%)
o4-09
(0525)
IGBT Maintenance
Setting
Sets the
U4-07 [IGBT Maintenance]
monitor value.
0%
(0 - 150%)
o4-11
(0510)
Fault Trace/History Init
(U2/U3)
Resets the records of Monitors
U2-xx [Fault Trace]
and
U3-xx [Fault History]
.
0 : Disabled
1 : Enabled
0
(0, 1)
V/f
CL-V/f
OLV
CLV
AOLV
V/f
CL-V/f
OLV
CLV
AOLV
V/f
CL-V/f
OLV
CLV
AOLV
V/f
CL-V/f
OLV
CLV
AOLV
V/f
CL-V/f
OLV
CLV
AOLV
V/f
CL-V/f
OLV
CLV
AOLV
V/f
CL-V/f
OLV
CLV
AOLV
V/f
CL-V/f
OLV
CLV
AOLV
V/f
CL-V/f
OLV
CLV
AOLV
V/f
CL-V/f
OLV
CLV
AOLV
V/f
CL-V/f
OLV
CLV
AOLV
V/f
CL-V/f
OLV
CLV
AOLV
V/f
CL-V/f
OLV
CLV
AOLV
Содержание CR700
Страница 1: ......
Страница 2: ...This Page Intentionally Blank 2 YASKAWA SIEPC71061723A YASKAWA AC Drive CR700 Technical Manual ...
Страница 244: ...3 13 Test Run Checklist 244 YASKAWA SIEPC71061723A YASKAWA AC Drive CR700 Technical Manual ...
Страница 422: ...7 7 Storage Guidelines 422 YASKAWA SIEPC71061723A YASKAWA AC Drive CR700 Technical Manual ...
Страница 426: ...8 2 Disposal Instructions 426 YASKAWA SIEPC71061723A YASKAWA AC Drive CR700 Technical Manual ...
Страница 837: ...EZZ023535 2 35 1 Revision History Revision Revised Content Date First Edition 2017 08 ...
Страница 872: ...EZZ023536 2 16 Revision History Revision Revised Content Date First Edition 2017 08 ...