13 Faults and Alarms

YASKAWA ELECTRIC

TOEP C710617 17D YASKAWA AC Drive GA700 Initial Steps

EN 29

No.

(Hex.)

Name

Description

H4-03

(041F)

RUN

Terminal FM Analog
Output Bias

Sets the bias of the

Ux-xx

monitor signal in

H4-01 [Terminal FM Analog Output Select]

.

H4-04

(0420)

Terminal AM Analog
Output Select

Sets which drive monitor

Ux-xx

to output from MFAO terminal AM.

H4-05

(0421)

RUN

Terminal AM Analog
Output Gain

Sets the gain of the

Ux-xx

monitor signal in

H4-04 [Terminal AM Analog Output Select]

.

H4-06

(0422)

RUN

Terminal AM Analog
Output Bias

Sets the bias of the

Ux-xx

monitor signal in

H4-04 [Terminal AM Analog Output Select]

.

H4-07

(0423)

Terminal FM Signal Level
Select

Sets the output signal level from MFAO terminal FM.
0: 0 to 10 Vdc, 1: -10 to +10 Vdc, 2: 4 to 20 mA

H4-08

(0424)

Terminal AM Signal
Level Select

Sets the output signal level from MFAO terminal AM.
0: 0 to 10 Vdc, 1: -10 to +10 Vdc, 2: 4 to 20 mA

L1-01

(0480)

Motor Overload (oL1)
Protection

Sets the motor overload protection function that uses electronic thermal protectors.
0: Disabled, 1: Variable Torque, 2: Constant Torque 10:1 Speed Range,
3: Constant Torque 100:1 SpeedRange, 4: PM Variable Torque, 5: PM Constant Torque,
6: Variable Torque (50Hz)

L1-02

(0481)

Motor Overload
Protection Time

Sets the motor overload (oL1) protection time. Usually it is not necessary to change this
setting.

L3-04

(0492)

Stall Prevention during
Decel

Sets the method that the drive will use to prevent overvoltage faults when decelerating.
0: Disabled, 1: General Purpose, 2: Intelligent (Ignore Decel Ramp),
3: General Purpose w/ DB resistor, 4: Overexcitation/High Flux,
5: Overexcitation/High Flux 2

13

Faults and Alarms

Look at the drive keypad for fault and alarm information if the drive or motor do not operate correctly.

For drive alarms:

Keypad shows the alarm code

and ALM/ERR on the LED Status Ring flash.

The drive will continue to operate the motor. Some alarms let the user select a motor stopping method.

For drive faults:

Keypad shows the fault code

and ALM/ERR on the LED Status Ring stay illuminated.

The drive shuts off output, the fault relay output turns ON, and the motor coasts to stop.

Fault Reset Procedure

1. Remove the cause of the fault or alarm.

2. Push

(Reset) or

on the keypad while the keypad is showing the fault or alarm code.

This table lists the most frequent alarms and faults with possible causes and solutions.

Refer to the Technical Manual for a full list of faults and alarms.

Code

Name

Causes

Possible Solutions

bb

Baseblock

A digital input set for the software
baseblock function is OFF and the drive
will not accept a Run command.

Make sure that the digital input function
selections are correct.

Make sure that the host controller sequence is
correct.

CrST

Remove RUN Command to
Reset

Tried to reset a fault when a Run
command was active.

Stop the Run command and reset the drive.

EN

Содержание CIPR-GA70C Series

Страница 1: ...Performance Type Initial Steps Type CIPR GA70Cxxxxxxxx Models 200 V class 0 55 to 110 kW 400 V class 0 55 to 355 kW To properly use the product read this manual thoroughly and retain for easy referen...

Страница 2: ...dynamically detect failures and operate safely without exception All products that are designed to incorporate parts manufactured by Yaskawa must be provided to the end user and include proper warning...

Страница 3: ...Tighten screws against the bit at an angle in the specified range described in this manual Tightening screws at an angle outside of the specified range can cause damage the terminal block or start a...

Страница 4: ...specified in this manual DANGER Electrical Shock Hazard Make sure that all electrical connections are correct and install all drive covers before energizing the drive Use terminals for their intended...

Страница 5: ...number in the MODEL section of the drive nameplate to make sure that you received the correct model Contact your supplier if you receive the incorrect drive model or if the drive does not operate cor...

Страница 6: ...ceived a Run command from the MFDI terminals when the drive is not in Drive Mode The drive received a Fast Stop command The safety function shuts off the drive output The user pushed on the keypad whi...

Страница 7: ...ive operation Note Uses a stop priority circuit Push to stop the motor even when a Run command is active at MFDI terminals Set o2 02 0 STOP Key Function Selection Disabled to disable the priority in H...

Страница 8: ...6 Keypad EN 8 YASKAWA ELECTRIC TOEP C710617 17D YASKAWA AC Drive GA700 Initial Steps Keypad Mode and Menu Displays Figure 6 2 Keypad Functions and Display Levels...

Страница 9: ...an external source while in Programming Mode Set b1 08 0 Disregard RUN while Programming to reject the Run command from an external source while in Programming Mode default Set b1 08 1 Accept RUN whil...

Страница 10: ...erate such as when in Programming Mode or when is flashing C RUN Illuminated The drive is in regular operation Flashing 1 The drive is decelerating to stop The drive received a Run command with a freq...

Страница 11: ...ically set these functions Control method selection Duty rating selection Monitor parameters Speed reference source Run command source Acceleration and deceleration times 5 Run the motor without a loa...

Страница 12: ...rect operation and damage to electrical devices Installation Position and Distance Install the drive vertically for sufficient cooling airflow Note Contact Yaskawa or a Yaskawa representative for more...

Страница 13: ...environment is crucial to ensure proper performance and the expected lifespan of the product Ensure the installation environment satisfies the following specifications Environment Conditions Area of U...

Страница 14: ...ear the drive Failure to obey can cause incorrect operation NOTICE Do not let unwanted objects for example metal shavings or wire clippings fall into the drive during drive installation and project co...

Страница 15: ...Keypad connector B Hook C Connector holder Figure 9 5 Remove the Front Cover 6 Remove the wiring cover before wiring the main circuit terminal A Wiring cover Remove the Terminal Cover 1 Loosen the scr...

Страница 16: ...before operating the drive Reattach the Front Cover 1 Reattach the wiring cover 2 Reattach the front cover to the drive with the supplied screws 3 Remove the keypad connector from the connector holder...

Страница 17: ...not maintain the IP20 protective level Hold the cutaway section of the wiring cover firmly to prevent scattering when clipping this section There is a risk of injury from scattering of the cutaway sec...

Страница 18: ...Incorrect Run Stop circuit sequence settings can cause death or serious injury from moving equipment WARNING Sudden Movement Hazard Correctly wire the start stop and safety circuits before energizing...

Страница 19: ...ergize the drive with the fault relay output Set L5 02 1 Fault Contact at Restart Select Always Active to de energize the drive when the drive outputs a fault during fault restart when using the fault...

Страница 20: ...o jumper necessary between terminals SC and SN or terminals SC and SP 12 The maximum output current capacity for terminals Vand Von the control circuit is 20 mA NOTICE Do not install a jumper between...

Страница 21: ...hat users must wire the power supply to automatically turn off when the protective ground wire disconnects Users can also connect a protective ground wire that has a minimum cross sectional area of 10...

Страница 22: ...quipment A Terminal block TB2 3 B Terminal block TB2 2 C Terminal block TB2 1 D DC bus voltage terminals configuration changes by drive model E Drive ground terminals F Motor case ground G Three phase...

Страница 23: ...F ambient temperature 3 Select Setup Wizard and follow the instructions shown on the keypad until the setup wizard completes The drive and motor are prepared for operation Auto Tuning WARNING Crush H...

Страница 24: ...test report data is not available YES Stationary Line Line Resistance 2 Select this tuning mode when The drive and motor capacities are different The drive is in V f Control Replacing the drive and m...

Страница 25: ...een the minimum value and maximum value 8 Push to keep the changes 9 Continue to set parameters or push Back to go back to the HOME screen 12 Drive Control Duty Modes and Programming Drive Control Met...

Страница 26: ...460 V 0 Extruder Conveyor Constant torque or high overload capacity 2 kHz 150 rated output current for 60 s Heavy Duty Rating 2 HD2 460 Vand 480 V Normal Duty Rating 1 ND1 200 Vand 240 V 380 Vand 460...

Страница 27: ...y Rating C6 02 0224 Carrier Frequency Selection Sets the carrier frequency for the transistors in the drive 1 2 0 kHz 2 5 0 kHz 4 0 kHz for AOLV PM 3 8 0 kHz 6 0 kHz for AOLV PM 4 10 0 kHz 8 0 kHz for...

Страница 28: ...A3 Function Selection Sets the function for MFAI terminal A3 H3 07 0415 RUN Terminal A3 Gain Setting Sets the gain of the analog signal input to MFAI terminal A3 H3 08 0416 RUN Terminal A3 Bias Settin...

Страница 29: ...ange this setting L3 04 0492 Stall Prevention during Decel Sets the method that the drive will use to prevent overvoltage faults when decelerating 0 Disabled 1 General Purpose 2 Intelligent Ignore Dec...

Страница 30: ...ect oL1 Motor Overload The motor load is too heavy Decrease the motor load Operating a general purpose motor slower than the rated speed with a high load Use a motor with external cooling and set the...

Страница 31: ...1 PL e Cat III and IEC EN 61508 SIL3 connect a jumper between terminals HC H1 and H2 SToF Safe Torque OFF Hardware Opening only one Safe Disable input disables drive output Usually inputs H1 and H2 m...

Страница 32: ...are subject to change without notice for ongoing product modifications and improvements 2016 YASKAWA Electric Corporation MANUAL NO TOEP C710617 17D 3 0 Published in Japan December 2016 15 11 8_YEU Or...

Отзывы: