20
Wiring
Grounding
Section 4
• The Drive must be solidly grounded using the main circuit ground terminal .
• If Drive is installed in a cabinet with other equipment, ground leads for all equipment should be connected to a
common low-impedance ground point within the cabinet.
• The supply neutral should be connected to the ground point within the cabinet.
•
Select appropriate ground wire size from Table 1-1.
•
Make all ground wires as short as practical.
•
NEVER ground the Drive in common with welding machines, or other high power electrical equipment.
•
Where several Drives are used, ground each directly to the ground point (see Figure 1-2). DO NOT FORM A
LOOP WITH THE GROUND LEADS.
•
When connecting a motor to the Drive’s output terminals, include a separate ground wire. Attach ground wire
solidly to motor frame and to Drive’s ground terminal .
•
When using armored or shielded cable for connection between Drive and motor, solidly connect armor or shield
to motor frame, and to the Drive’s ground terminal .
Figure 1-2. Correct Ground Connection
CORRECT
CORRECT
NOT
ACCEPTABLE
IG.V7.01_new format.qxd 4/18/05 1:21 PM Page 20
Содержание CIMR-V7xx20P1 series
Страница 4: ...4 IG V7 01_new format qxd 4 18 05 1 21 PM Page 4...
Страница 10: ...10 IG V7 01_new format qxd 4 18 05 1 21 PM Page 10...
Страница 14: ...14 IG V7 01_new format qxd 4 18 05 1 21 PM Page 14...
Страница 58: ...58 Drive Dimensions Section 10 Fig 4 W W W H1 H H2 4 d D IG V7 01_new format qxd 4 18 05 1 21 PM Page 58...
Страница 60: ...IG V7 01_new format qxd 4 18 05 1 21 PM Page 60...
Страница 61: ...IG V7 01_new format qxd 4 18 05 1 21 PM Page 61...
Страница 62: ...IG V7 01_new format qxd 4 18 05 1 21 PM Page 62...
Страница 63: ...IG V7 01_new format qxd 4 18 05 1 21 PM Page 63...