B.2 Parameter Tables
YASKAWA ELECTRIC
TOEP C710656 10B YASKAWA Power Regenerative Unit - R1000 Instruction Manual
151
Pa
ra
me
te
r L
is
t
B
12
Timer output
Timer Output
Closed: Timer output.
1B
During baseblock (N.C.)
BaseBlk 2
Open: Regenerative unit has entered the baseblock state (no
regeneration).
1D
During Regeneration
Regenerating
Closed: Motor is regenerating energy into the regenerative unit.
1E
Restart enabled
Dur Flt Restart
Closed: An automatic restart is performed
20
Heatsink Overheat (oH)
pre-alarm
OH Prealarm
Closed: Heatsink temperature exceeds the parameter L8-02 value.
24
Fuse Blowout Detection
FUA/FUD Detect
Closed: Fuse burnout detected.
25
During Run 1
During RUN 1
Closed: The drive is ready to operate.
26
During MC ON
MC On
Closed: The magnetic contactor is closed.
27
Overload (oL2) Warning
OL2 Pre-alarm
Closed: There is an overload warning.
2F
Maintenance Period
Maintenance
Closed: It is time to perform maintenance on the cooling fan, electrolytic
capacitor, and inrush prevention relay.
3A
kWh Monitor Pulse Output Power
(Produced)
Set the unit in H2-06.
Multi-function output is ON for 200 ms depending on the unit selected in
H2-06.
3B
Alarm 2
Minor Fault 2
Closed: Alarm occurred (excluding Uv, AUv, Fdv, SrC, and PAUv).
Note:
This setting is available in regenerative unit software versions
PRG:2003 or later.
3C
LOCAL/REMOTE status
Local
Open: REMOTE
Closed: LOCAL
4D
oH Pre-alarm time limit
OH Pre-Alarm
Closed: oH pre-alarm time limit has passed.
60
Internal cooling fan alarm
Fan Alrm Det
Closed: Internal cooling fan alarm
100 to 160
Function 0 to 60 with inverse
output
–
Inverts the output switching of the multi-function output functions.
Set the last two digits of 1
to reverse the output signal of that
specific function.
No.
(Address
Hex)
Name
LCD Display
Description
Values
H3: Multi-Function Analog Inputs
H3-01
(410H)
Terminal A1 Signal
Level Selection
Term A1 Level
0: 0-10V, (LowLim=0)
1: 0-10V, (BipolRef)
0: 0 to 10 V
1: -10 to 10 V
Default: 0
Min.: 0
Max.: 1
H3-02
(434H)
Terminal A1
Function Selection
Term A1 FuncSel
Sets the function of terminal A1.
Default: F
Min.: F
Max.: F
H3-03
(411H)
Terminal A1 Gain
Setting
Terminal A1 Gain
Sets the level of the input value selected in H3-02 when 10
V is input at terminal A1.
Default: 100.0%
Min.: -999.9%
Max.: 999.9%
H3-04
(412H)
Terminal A1 Bias
Setting
Terminal A1 Bias
Sets the level of the input value selected in H3-02 when 0
V is input at terminal A1.
Default: 0.0%
Min.: -999.9%
Max.: 999.9%
H3-05
(413H)
Terminal A3 Signal
Level Selection
Term A3 Signal
0: 0-10V (LowLim=0)
1: 0-10V (BipolRef)
0: 0 to 10 V
1: -10 to 10 V
Default: 0
Min.: 0
Max.: 1
H3-06
(414H)
Terminal A3
Function Selection
Terminal A3 Sel
Sets the function of terminal A3.
Default: F
Min.: F
Max.: F
H3-07
(415H)
Terminal A3 Gain
Setting
Terminal A3 Gain
Sets the level of the input value selected in H3-06 when 10
V is input at terminal A3.
Default: 100.0%
Min.: -999.9%
Max.: 999.9%
H3-08
(416H)
Terminal A3 Bias
Setting
Terminal A3 Bias
Sets the level of the input value selected in H3-06 when 0
V is input at terminal A3.
Default: 0.0%
Min.: -999.9%
Max.: 999.9%
H2 Multi-Function Relay Output Settings
H2-
Setting
Function
LCD Display
Description