10.2 Precautions for Complying with European Standards
10-5
Standards Compliance
0
1
10.2.3
Compliance with Low Voltage Directive
This drive has been tested according to European standard IEC61800-5-1, and it fully complies with the Low
Voltage Directive.
To comply with the Low Voltage Directive, be sure to meet the following conditions when combining this
drive with other devices.
(1) Installation Location
Install the servo drive in a location with an overvoltage category of 3 and a pollution degree of 2 or lower
according to IEC 664 specifications. Install at an altitude of 1000 m max.
(2) Protection against Foreign Matter
The degree of protection of the servo drives is IP10.
(3) Grounding
Ground the neutral point of the 400-V power supply. The leakage current may exceed 3.5 mA. Therefore, use
a 10-mm
2
or thicker copper grounding wire.
(4) 24-VDC Control Power Supply
Use a 24-VDC control power supply with double insulation or reinforced insulation against primary.