background image

 16 

AB-6474 

Maintenance 

Since the temperature/humidity sensor is inspected and 
calibrated for high accuracy at the factory before 
shipment, no field calibration is necessary.  Follow the  
maintenance instructions below. 

1)   Periodic inspection 

Determine the frequency of periodic inspection 
depending on the amount of suspended dust and 
other contaminants in the environment.  Regulary 
check the sensing accuracy and clean the cover. 

2)   Troubleshooting 

If any problem occurs during operation, refer to the 
following table for appropriate solutions. 

 

Troubleshooting and Solution 

Problems Check 

items Solutions 

 No output 

generated 

 Unstable output

 

 Loose wiring 

 Disconnected 

wiring 

 Power supply 

voltage 

 Sensor damages 

 Re-perform wiring. 

 
 
 
 

 Replace sensor.

 

 Slow response to 

output 

 

 Moisture/conden- 

sation on the 
sensor 

 

 

 Remove cover. 

 Dry power-off 

state sensor in 
clean air 
seasoning. 

 Error in output 

 Installed location 

 Dust and 

contamination on 
the sensor 

 Refer to   

‘Installation 
requirements’. 

 Clean the cover. 

 Perform humidity 

single-point 
calibration. 

 Replace the 

sensor. 

 

 

3)  Humidity single-point calibration (Models HTY7043T, 

HY7043T) 
When you find an output error of the humidity sensor, 
the sensor can be calibrated with the adjustment 
knobs,VR1 for rough adjustment, VR2 for fine 
adjustment, located inside the humidity sensor.    The 
output value is increased by turning these knobs 
clockwise and decreased by turning them 
counterclockwise. 
Use a reliable measuring instrument for humidity 
single-point calibration with correct procedure in 
appropriate environment.  A digital multimeter is 
recommended to check the output voltage. 

Fig. 20      Adjustment knobs arrangement on the circuit board 

Cautions 

1. Leave the unpacked sensor in the ambient 

atmosphere for approx. 24 hours. 

2.  Be sure not to affect the sensor with heat generation 

from human body and/or appliances during the sensor 
calibration. 

 

 

 

 

 

 

 

 
 

 

 

Building Systems Company     

 
Tamachi Kiyota Building     
4-3-4, Shibaura 
Minato-ku, Tokyo 108-0023 
http://www.yamatake.com 
 
Rev. 2.1  Apr. 2005 

AB-6474 0.5H-H (W00) 

(J: AI-6474 Rev. 2.1) 

 

 

Fine adjustment knob (VR1) 

Temperature sensing 
element 

Humidity sensing element 

Rough adjustment knob (VR2) 

Specifications are subject to change without notice. 

16 

Содержание Neosensor HTY7043

Страница 1: ...43 uses a Pt100 resistance thermometer sensor JIS C1604 Class A for a temperature sensing element and a polymer capacitive humidity sensor FP3 TM specially developed by Yamatake Corp for a humidity sensing element enhancing accuracy and reliability of temperature humidity sensing It is suitable for various applications such as commercial buildings or other indoor uses JIS Japanese Industrial Stand...

Страница 2: ... out under the operating conditions specified in this manual to prevent equipment damages Always disconnect power source before performing any wiring to prevent equipment damages All wiring must comply with local codes of indoor wiring and electric installation rules Do not disassemble the product at any time except when removing the cover to install the product main unit Equipment damages may occ...

Страница 3: ...efer to the table below Available model numbers HTY7043T1P00 With company logo HTY7043T1P00 1 Humidity 1 5 V DC Temperature Pt100 Neosensor Without company logo TY7043Z0P00 With company logo TY7043Z0P00 1 Temperature Pt100 Neosensor Without company logo TY7053Z0P00 With company logo TY7053Z0P00 1 Temperature Pt100 High Sensitivity Neosensor Without company logo TY7043Z0P01 With company logo TY7043...

Страница 4: ...o 80 RH 15 C to 35 C Conditions 24 V DC input power supply 250 Ω resistive load 0 15 m s wind velocity and 60 minute warm up period Temperature Neosensor 4 5 minutes or less High Sensitivity Neosensor 2 5 minutes or less Reference values Time constant for wind velocity of 0 15 m s Humidity Neosensor 40 seconds or less Temperature Rated operating conditions Models HTY7043T and TY70X3Z series 0 C to...

Страница 5: ...room control Models QY1100C QY1100D with rotary switch Thermoplate Model DY2000A1022 1 unit lengthwise mounting Model DY2000A1023 1 unit crosswise mounting Model DY2000A2023 2 unit crosswise mounting with outlet box Model DY2000A2024 2 unit crosswise mounting with switch box Model DY2000A3022 3 unit crosswise mounting Conduit connection type Thermoplate Model DY2000A1021 1 unit square mounting Mod...

Страница 6: ...ounting kit 45 5 16 5 77 90 77 15 15 80 Mounting screw M3 φ4 2 mounting hole Mounting hole 66 7 80 Note When mounting the Neosensor be sure to secure a longer than 15 mm clearance for wiring from the mounting surface inside the wall Note When mounting the Neosensor be sure to secure a longer than 15 mm clearance for wiring from the mounting surface inside the wall 8 2 4 2 Use JIS outlet box box co...

Страница 7: ...f Thermoplate mounting kit Figure 2 Dimensions mm Thermoplate mounting Note When mounting the Neostat be sure to secure a longer than 12 5 mm clearance for wiring from the mounting surface inside the wall 77 48 77 77 12 5 19 Thermoplate mounting kit 77 Mounting surface Note When mounting the Neostat be sure to secure a longer than 12 5 mm clearance for wiring from the mounting surface inside the w...

Страница 8: ...lti Thermocase mounting Multi Thermocase mounting kit 85 23 72 8 52 Assembled dimension of device mounting plate of Multi Thermocase and Multi Thermocase mounting kit 66 7 mm 72 8 85 72 8 72 8 85 68 55 φ3 4 mounting hole 66 7 When multiple units of Neosensor and or Neostat are installed in a Multi Thermocase separate order required the Neosensor main unit covers are not used ...

Страница 9: ...n a wall See Fig 4 1 Attach the mounting plate to the box cover outlet box mounting dimension 66 7 mm JIS C8340 1999 located inside the wall 2 Install the main part of the Wall direct mounting kit on the mounting plate See Fig 9 3 Connect the output lead wires of the Neosensor main unit to the external wires for the load side See Figs 15 and 16 4 Remove the cover from the Neosensor main unit and m...

Страница 10: ...Wall direct mounting kit make sure to set the height adjusting levers on the left and right sides See Fig 12 to the upper position indicated by L 5 Reinstall the cover to the main unit to complete the installation procedure See Fig 8 Figure 5 Installation Neosensor with Wall direct mounting kit on conduit connection type Thermoplate 66 7 Accessory screws 4 flat head machine screws M3 16 External w...

Страница 11: ...unit onto the Thermoplate mounting kit make sure to set the height adjusting levers on the left and right sides See Fig 12 to the upper position indicated by L 6 Place the cover back on the Neosensor main unit to complete the installation procedure See Fig 8 Figure 6 Installation Neosensor with Thermoplate mounting kit on Thermoplate Output lead wires Thermoplate mounting kit separate order requir...

Страница 12: ...mocase be sure to set the height adjusting levers on the left and right sides of the Neosensor main unit to the lower position indicated by H Figure 7 Installation Neosensor in Multi Thermocase with Multi Thermocase mounting kit Note To mount the Neosensor main unit set the height adjusting lever on the left and right sides to the lower position before fixing the main unit on the Multi Thermocase ...

Страница 13: ...ng kit Max 9 mm Figure 11 Pulling up the Neosensor main unit 3 Lower the height adjusting levers on the left and right The height adjusting levers are set to the upper position indicated by L for factory preset Figure 12 Height adjusting lever 4 Mount and fix the Neosensor main unit ont the main part of the Wall direct mounting kit with the 4 mounting screws Figure 13 Neosensor mounting on the Wal...

Страница 14: ...ng Always check wiring before supplying power Never share 24 V AC transformer with any other product Figure 17 Wiring diagram Black lines for power supply and for humidity output are connected inside the Neosensor Model HY7043T1000 Model TY7043Z0P00 Model TY7053Z0P00 Pt100 Brown Black Blue Black Red White White A B B 24 V AC 24 V DC 1 5 V DC J1 1 A 2 B 3 A 4 B 5 NC 6 B 7 NC 8 B Model TY7043Z0P01 M...

Страница 15: ...ontroller with a low pass filter removal ratio of 40dB or higher in normal mode for receiving signals Connect an isolator for the controller input circuit if a removal ratio is not enough No problem will occur for connecting with a Yamatake s controller DC power supply can be shared Though loop is formed at common common mode noise affects a little Correct 24 V DC Temperature humidity sensor Tempe...

Страница 16: ...m humidity single point calibration Replace the sensor 3 Humidity single point calibration Models HTY7043T HY7043T When you find an output error of the humidity sensor the sensor can be calibrated with the adjustment knobs VR1 for rough adjustment VR2 for fine adjustment located inside the humidity sensor The output value is increased by turning these knobs clockwise and decreased by turning them ...

Отзывы: