AB-5963

Troubleshooting

Problem…

Check…

Action…

- No output

generated

- Unstable output

- Check loose

connection

- Check Incorrect

wiring

- Check supply voltage
- Check sensor

damage

- Tighten the terminal

brock

- Re-wire

- Replace sensor

- Slow response

- Error in output

- Check the sensor for

water leakage or
condensation

- Check the installed

location

- Check the dust, soil.

- Remove the unit from

bracket.
Dry the unit with no
power.

- Refer to the

Installation
instructions

- Clean filter
- Replace filter
- Humidity one point

adjustment

- Replace the product

3) Replacing the filter:

(1) Prepare filter set (order separately) in advance.

Remove the filter cap and filter by hand.

(2) Cover the sensor with the new filter and then put

the new filter cap over.

(3) Tighten the filter cap.

4) Humidity one point adjustment

When you find a calibration error in the humidity sen-
sor, re-calibrate the sensor using the adjustment vol-
ume (VR1, VR2) located on the circuit board. The out-
put value is increased by turning this volume in clock-
wise direction and decreased by turning it counter-
clockwise.    Use refelenced humidity meter of ade-
quate accuracy.    A digital multimeter is recommend-
ed to check the output voltage.

Parts Identification of adjustment volume

Cautions

1. After unpacking, age the transmitter in the ambient

atmosphere for at last 24 hours.

2. To calibrate and adjust, take care the heat from human

body or appliances.

3. When one-point adjustment is done at an environment

where relative humidity is higher than 50 % RH, the
dewpoint temperature accuracy specifications may not
be met to where relative humidity is under 50 % RH.

Yamatake Building Systems Co., Ltd.

Yamatake Corporation
International Business Division

Totate International Bldg.
2-12-19, Shibuya, Shibuya-Ku
Tokyo, 150-8316, Japan
Phone:

81-3-3486-2350

Facsimile:

81-3-3486-2592

Rev. 1.0 Dec. 2000

Printed in Japan.    AB-5963 0.5H-H (W)

Specifications are subjects to change without notice.

Filter cap (The cap will remove
with the filter inside.)

Loosen

Filter cap

Filter

Filter cap

Tighten

Rough adjustment knob (VR2)

Fine adjustment knob (VR1)

Содержание HTY79

Страница 1: ...ensing only dewpoint temperature without separate temperature sensor is also available Features 1 Wide sensing range 2 Excellent long term stability 3 Highly resistant to environment 4 Quick response and high repeatability 5 Easy to install in a duct bracket prepared 6 Splash proof housing IP54 Models Model No Shape Type Power supply Humidity output Temperature output Fixed Fixed Description HTY79...

Страница 2: ...for reference at any time Usage Restrictions This product is targeted for general air conditioning Do not use this product in a situation where human life may be affected If this product is used in clean rooms or places where reliability or control accuracy is particularly required please contact Yamatake s sales representatives Yamatake Building Systems Co Ltd bears no responsibility for any bene...

Страница 3: ...Yseries Power consumption 0 6 VA at conditions of 24 V AC HTY HY series 1 5 V 0 10 V output model 450 mW at conditions of 24 V DC HTY HY series 1 5 V 0 10 V output model 1 4 VA at conditions of 24 V AC HTY HY series 4 20 mA output model 1 2 W at conditions of 24 V DC HTY HY series 4 20 mA output model Dielectric strength 500 VAC less than 1 mA of leak for 1 minute Insulation resistance 500 VDC min...

Страница 4: ...4 AB 5963 Dimensions mm 1 7903 series 2 7913 series 3 Mounting bracket 62 5 25 50 60 40 60 72 3 φ30 3 3 247 6 51 3 45 6 67 3 A 70 φ20 110 1135 A 108 6 51 3 45 6 67 3 70 φ20 110 1135 ...

Страница 5: ...t the point indicated on the label Fix the mounting bracket onto the duct with M4 screws inserting packing between the duct and the bracket Cover the duct with an insulating material If you cover the duct with an insulating material first fill the clearance between the bracket and the duct with the insulating material after fixing the bracket 2 Turn the stopper of the main unit to the left and ins...

Страница 6: ...e conduit at a point where the conduit lock screw can be tightened easily 2 Connect the wires to the terminals and close the cover Tighten the seal connector only when cable connected Terminal Nos and cable cores Seal connector order separately Nut attached to conduit Attachment Conduit connector nominal size 25 mm Pull the cable Tightening direction Nut attached to conduit Conduit connector nomin...

Страница 7: ... generating noise due to inadequate time constant of the controller input Use a controller with a low pass filter with a removal ratio of 40 dB or higher normal mode Connect an isolator to the controller input circuit if a removal ratio is unknown If you use a Yamatake cotnroller no problem will occur Maintenance Since the temperature humidity sensor have been in spected and adjusted accurately be...

Страница 8: ...d The out put value is increased by turning this volume in clock wise direction and decreased by turning it counter clockwise Use refelenced humidity meter of ade quate accuracy A digital multimeter is recommend ed to check the output voltage Parts Identification of adjustment volume Cautions 1 After unpacking age the transmitter in the ambient atmosphere for at last 24 hours 2 To calibrate and ad...

Отзывы: