7

AB-5963

Wiring Instructions

Shielded multi-core cables (CVV-S) of 1.25 mm² or 2
mm² are recommended.    Be sure to ground the shielded
cable on the controller side.

If you don't need splashproof, a 1.25 mm² or 2 mm² IV
cable may be used for power and a 1.25 mm² shielded
cable for humidity and temperature signals.

The maximum cable length is 100 m.

Never connect power supply to temperature output.

Always check wiring before supplying power.

Never share 24V AC transformer to other products.

Use of individual AC transformer of humidity
transimitter

 CAUTION

Use insulated transformer to supply 24 V AC
power supply voltage.
Never share 24 V AC power supply with other
equipment.
If a transformer is shared with other equipment,
loop will be formed at common and the
sensor/transmitter may be damaged.

 

Transformer (24 V AC power supply) shared

 

Transformer (24 V AC) separated

 

24 V DC power shared

Follow the next instructions to prevent an induction cur-
rent flowing from the humidity sensor to the controller
input circuit, or to prevent an influence on the generating
noise due to inadequate time constant of the controller
input.

 

Use a controller with a low pass filter with a removal
ratio of 40 dB or higher (normal mode).

 

Connect an isolator to the controller input circuit if a
removal ratio is unknown.

 

If you use a Yamatake cotnroller, no problem will
occur.

Maintenance

Since the temperature / humidity sensor have been in-
spected and adjusted accurately before shipment, they
need no adjustment at the site. However, follow the
maintenance instructions below :

1) Periodical inspection

Determine the periodical inspection intervals according
to the amount of suspended dust and other
contaminants in the environment.    Regulary check the
sensor’s accuracy and the condition of its cover.

2) Troubleshooting

If any problem occurs during operation, refer to the
following table for appropriate solutions.

No common loop formed

Common loop formed, however, not so
affected by common mode noise.

Good

24 V DC

Temperature / humidity sensor

Common loop formed

Not Good

24 V AC

Multi-loop
controller

Common
share

Temperature / humidity sensor

Good

24 V AC

24 V AC

Multi-loop
controller

Temperature / humidity sensor

Temperature / humidity sensor

Multi-loop
controller

Temperature / humidity sensor

Temperature / humidity sensor

Содержание HTY79

Страница 1: ...ensing only dewpoint temperature without separate temperature sensor is also available Features 1 Wide sensing range 2 Excellent long term stability 3 Highly resistant to environment 4 Quick response and high repeatability 5 Easy to install in a duct bracket prepared 6 Splash proof housing IP54 Models Model No Shape Type Power supply Humidity output Temperature output Fixed Fixed Description HTY79...

Страница 2: ...for reference at any time Usage Restrictions This product is targeted for general air conditioning Do not use this product in a situation where human life may be affected If this product is used in clean rooms or places where reliability or control accuracy is particularly required please contact Yamatake s sales representatives Yamatake Building Systems Co Ltd bears no responsibility for any bene...

Страница 3: ...Yseries Power consumption 0 6 VA at conditions of 24 V AC HTY HY series 1 5 V 0 10 V output model 450 mW at conditions of 24 V DC HTY HY series 1 5 V 0 10 V output model 1 4 VA at conditions of 24 V AC HTY HY series 4 20 mA output model 1 2 W at conditions of 24 V DC HTY HY series 4 20 mA output model Dielectric strength 500 VAC less than 1 mA of leak for 1 minute Insulation resistance 500 VDC min...

Страница 4: ...4 AB 5963 Dimensions mm 1 7903 series 2 7913 series 3 Mounting bracket 62 5 25 50 60 40 60 72 3 φ30 3 3 247 6 51 3 45 6 67 3 A 70 φ20 110 1135 A 108 6 51 3 45 6 67 3 70 φ20 110 1135 ...

Страница 5: ...t the point indicated on the label Fix the mounting bracket onto the duct with M4 screws inserting packing between the duct and the bracket Cover the duct with an insulating material If you cover the duct with an insulating material first fill the clearance between the bracket and the duct with the insulating material after fixing the bracket 2 Turn the stopper of the main unit to the left and ins...

Страница 6: ...e conduit at a point where the conduit lock screw can be tightened easily 2 Connect the wires to the terminals and close the cover Tighten the seal connector only when cable connected Terminal Nos and cable cores Seal connector order separately Nut attached to conduit Attachment Conduit connector nominal size 25 mm Pull the cable Tightening direction Nut attached to conduit Conduit connector nomin...

Страница 7: ... generating noise due to inadequate time constant of the controller input Use a controller with a low pass filter with a removal ratio of 40 dB or higher normal mode Connect an isolator to the controller input circuit if a removal ratio is unknown If you use a Yamatake cotnroller no problem will occur Maintenance Since the temperature humidity sensor have been in spected and adjusted accurately be...

Страница 8: ...d The out put value is increased by turning this volume in clock wise direction and decreased by turning it counter clockwise Use refelenced humidity meter of ade quate accuracy A digital multimeter is recommend ed to check the output voltage Parts Identification of adjustment volume Cautions 1 After unpacking age the transmitter in the ambient atmosphere for at last 24 hours 2 To calibrate and ad...

Отзывы: