6

AB-5963

Wiring (common instructions for 7903 series
and 7913 series)

1) Dismount the cover.

(i) Cable connection
Prepare the proper seal connector (order separately) in
advance, if required.
Screw the threaded seal connector into the main and
lead the cable through it.

(ii) Conduit connection
According to the number of cable cores, prepare a
conduit set (order separately) in advance.    Fix the
conduit connector and the attachment tentatively with a
screw.    Select an O-ring ideal for the cable.

Lead the cable, as shown in the following diagram.
Pull up the cable and fix the attachment to the main unit
with a screw.
Tighten the nut on the conduit at a point where the
conduit lock screw can be tightened easily.

2) Connect the wires to the terminals and close the cover.

Tighten the seal connector. (only when cable
connected)

Terminal Nos. and cable cores

Seal connector
(order separately)

Nut attached to
conduit

Attachment

Conduit connector
(nominal size: 25 mm)

Pull the cable

Tightening direction

Nut attached to conduit

Conduit connector
(nominal size: 25 mm)

Straight box connector
(nominal size: 24-25 mm)

Conduit lock
screw

Attachment

O-ring

Tighten

Allow sufficient
service clearance

(+)

Pt 100

1

2

3

4

5

6

7

A

B

B

24 V AC

(24 V DC)

1-5 V DC

0-10 V DC

4-20 mA

HTY7903T1P00

HTY7903T4P00

HTY7903T6P00

HTY7913T1P00

HTY7913T4P00

HTY7913T6P00

(Cable cores:7)

(–)

+

HY7903T1000
HY7903T4000
HY7903T6000
HY7913T1000
HY7913T4000
HY7913T6000
(Cable cores:4)

Power
supply

Dewpoint

Tempe
rature

Содержание HTY79

Страница 1: ...ensing only dewpoint temperature without separate temperature sensor is also available Features 1 Wide sensing range 2 Excellent long term stability 3 Highly resistant to environment 4 Quick response and high repeatability 5 Easy to install in a duct bracket prepared 6 Splash proof housing IP54 Models Model No Shape Type Power supply Humidity output Temperature output Fixed Fixed Description HTY79...

Страница 2: ...for reference at any time Usage Restrictions This product is targeted for general air conditioning Do not use this product in a situation where human life may be affected If this product is used in clean rooms or places where reliability or control accuracy is particularly required please contact Yamatake s sales representatives Yamatake Building Systems Co Ltd bears no responsibility for any bene...

Страница 3: ...Yseries Power consumption 0 6 VA at conditions of 24 V AC HTY HY series 1 5 V 0 10 V output model 450 mW at conditions of 24 V DC HTY HY series 1 5 V 0 10 V output model 1 4 VA at conditions of 24 V AC HTY HY series 4 20 mA output model 1 2 W at conditions of 24 V DC HTY HY series 4 20 mA output model Dielectric strength 500 VAC less than 1 mA of leak for 1 minute Insulation resistance 500 VDC min...

Страница 4: ...4 AB 5963 Dimensions mm 1 7903 series 2 7913 series 3 Mounting bracket 62 5 25 50 60 40 60 72 3 φ30 3 3 247 6 51 3 45 6 67 3 A 70 φ20 110 1135 A 108 6 51 3 45 6 67 3 70 φ20 110 1135 ...

Страница 5: ...t the point indicated on the label Fix the mounting bracket onto the duct with M4 screws inserting packing between the duct and the bracket Cover the duct with an insulating material If you cover the duct with an insulating material first fill the clearance between the bracket and the duct with the insulating material after fixing the bracket 2 Turn the stopper of the main unit to the left and ins...

Страница 6: ...e conduit at a point where the conduit lock screw can be tightened easily 2 Connect the wires to the terminals and close the cover Tighten the seal connector only when cable connected Terminal Nos and cable cores Seal connector order separately Nut attached to conduit Attachment Conduit connector nominal size 25 mm Pull the cable Tightening direction Nut attached to conduit Conduit connector nomin...

Страница 7: ... generating noise due to inadequate time constant of the controller input Use a controller with a low pass filter with a removal ratio of 40 dB or higher normal mode Connect an isolator to the controller input circuit if a removal ratio is unknown If you use a Yamatake cotnroller no problem will occur Maintenance Since the temperature humidity sensor have been in spected and adjusted accurately be...

Страница 8: ...d The out put value is increased by turning this volume in clock wise direction and decreased by turning it counter clockwise Use refelenced humidity meter of ade quate accuracy A digital multimeter is recommend ed to check the output voltage Parts Identification of adjustment volume Cautions 1 After unpacking age the transmitter in the ambient atmosphere for at last 24 hours 2 To calibrate and ad...

Отзывы: