4-2
■
Connection points and required parts
■
Recommended crimp-type terminal lug and tightening torque
Handling Precautions
• To prevent the short circuit in case of the screws' loosening, use the
Crimp type terminal lug with insulator.
• The tightening torque should be 0.4 to 0.5N·m for power supply terminals,
and 1.0 to 1.2N·m for communication terminals.
(Please note that the tightening torque for the mounting brackets is
different.)
Chapter 4. CONNECTIONS AND SETUP
Terminal
X
Screw
Recommended
Suitable cross-sectional
Parts No. of
crimp contact
area of the wire
J.S.T. MFG CO., Ltd
[mm]
JIS specifications
[mm
2
]
Power supply
6.4
terminal
M3
RAV1.25-3
0.25 to 1.65
V1.25-3
Communication
7.2
terminal
Connection points
Required parts
Power supply terminal,
Crimp type terminal lug
CH2, CH3, CH4, terminal block
CH1 9pins DSUB connector
DDK Ltd. 17JE-13090-02(D8C2) or the equivalent
DC input/output connector
EST side
J.S.T. MFG CO,.LTD B5B-XH-AM
Recommended connector
Housing J.S.T. MFG CO,.LTD XHP-5
Contact J.S.T. MFG CO,.LTD BXH-001T-P0.6
(for AWG28 to 22(0.08 to 0.33mm
2
), single-
unit selling)
Xmm