7800 SERIES EC7885A/RM7885A RELAY MODULE
65-0203
3
Electrical Ratings, EC7885A see Table 1B:
Voltage and Frequency: 200 Vac (+10/-15%), 50 or 60 Hz
(+/- 10%)
2
.
Power Dissipation: RM7885A: 10W maximum.
Maximum Total Connected Load: 2000 VA.
Fusing: Total Connected Load: 20A maximum, type FRN
or equivalent.
Environmental Ratings:
Ambient Temperature:
Operating: -40
°
F to 140
°
F.
Storage: -60
°
F to 150
°
F.
Humidity: 85% RH continuous, noncondensing.
Vibration: 0.5G environment.
Dimensions:
Refer to Fig. 1 and 2.
Weight:
7885A with Dust Cover: 1 pound 13 ounces, unpacked.
IMPORTANT
Flame Detection System available for use with
7885A. To select your Plug-in Flame Signal Amplifier
and applicable Flame Detector, see Table 2 and Fig.
3 through 5.
Terminal No.
Description
Ratings
G
Flame Sensor Ground
Earth G
Earth Ground.
1
L2(N)
Line Voltage Common
3
Line Voltage Supply (L1)
200 Vac (+10/-15%), 50 or 60 Hz (+/- 10%).
2,3
4
Alarm
200 Vac, 1A pilot duty.
5
Unused
6
Stop Station
200 Vac, 9A.
7
Unused
8
Pilot Valve
200 Vac, 4A at PF=0.5, 20A inrush.
9
Main Fuel Valve
200 Vac, 4A at PF=0.5, 20A inrush.
10
Start Input
200 Vac, 4A at PF=0.5, 20A inrush.
F(11)
Flame Sensor
60 to 220 Vac, current limited.
12
Unused
13
Unused
14
Unused
15
Unused
16
Unused
17
Unused
18
Unused
19
Unused
20
Unused
21
Unused
22
Shutter
200 Vac, 0.5A
1
The EC7885A must have an earth ground providing a connection between the subbase and the control panel or the equipment. The earth ground wire must
be capable of conducting the current to blow the 20A fuse in event of an internal short circuit. The EC7885A needs a low impedance ground connection to the
equipment frame that, in turn, needs a low impedance connection to earth ground. For a ground path to be low impedance at RF frequencies, the connection
must be made with minimum length conductors having maximum surface areas. Wide straps or brackets rather than leadwires are preferred. Be careful to
verify that mechanically tightened joints along the ground path, such as pipe or conduit threads or surfaces held together with fasteners, are free of
nonconductive coatings and are protected against mating surface corrosion.
2
Range of allowable operating frequency: 45 to 66 Hz.
3
2000 VA maximum connected load to EC7885A Assembly.
Table 1B. EC7885A Terminal Ratings.